| Notes |
| Date |
Text |
| 2014-10-14 17:14:21 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | 1- SHEET #1: | | | A) DESIGN CRITERIA: ENGINEER SPECIFIES "WIND SPEED = | | | 170 MPH NOMINAL 3 SEC GUST". DOOR AND WINDOW PRESSURES | | | ON SHEET 4 OF 7 DON'T CORRESPOND TO 170 MPH NOMINAL | | | WIND SPEED. REVISE AS REQUIRED. | | | B) ALTERATION LEVEL SHOWN UNDER "BUILDING TYPE" DOESN'T | | | MATCH ALTERATION LEVEL SHOWN UNDER DESIGN CRITERIA. | | | REVISE AS REQUIRED. | | | | | | 2- SHEET #5: | | | A) REVISE TREAD DIMENSION OF NEW STAIR DETAIL. SEE SEC. | | | R311.7.4.2. | | | B) SLIDING GLASS DOORS WERE CHANGED TO FRENCH DOORS. | | | NEED TO PROVIDE A LANDING IF MORE THAN 2 RISERS. SEC. | | | R311.3. REVISE PLANS AS REQUIRED. | | | | | | 3- PROVIDE 2 COPIES OF PRODUCT APPROVALS (DCA RULE | | | 9N-3) FOR: | | | A) ARCHED ENTRY DOOR AS SHOWN ON PLANS. |
|