| 2014-07-29 07:08:09 | | | | BUILDING PLAN REVIEW | | | PERMIT: 14070364 | | | ADD: 401 CLEMATIS ST | | | CITY HALL PARKING GARAGE/ DIESEL FUEL STORAGE | | | CONT: TBD | | | TEL: VIVEK 794-1061 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: TUES. JULY 29/2014 | | | ACTION: BUILDING PROVISO | | | | | | BUILDING APPROVED WITH EXCEPTION! | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE | | | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. | | | | | | 1) SHEET A-1.02 THE HOLE CORE DRILLED THROUGH THE 2ND | | | FLOOR GARAGE FLOOR SLAB FOR DETERMINING THE FLOOR FIRE | | | RESISTANCE IN HOURS IS TO BE PROTECTED. THE 2010 FBC-B | | | 713.4.1.1. THROUGH PENETRATIONS. THIS IS BUILDING TYPE | | | IIB CONSTRUCTION, FLOOR REQUIRED FIRE RATING IS 2 HRS. | | | 2010 FBC-B 721.2.2.1.2. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|