| Plan Review Notes For Permit 14070349 |
| Permit Number |
14070349 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-07-11 07:40:05 | ****CORRECTIONS**** | | | ****REVISED 8/13/14**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PROVIDE ENGINEERING FOR PROPOSED STRUCTURE, FBC | | | 1609. ENGINEERING FOR THE FOUNDATION WERE PROVIDED. | | | SOME SPEC SHEETS FOR THE PROPOSED SHADE STRUCTURE WERE | | | PROVIDED, BUT ENGINEERING PROVIDED APPEARS TO BE FOR | | | THE FOUNDATION ONLY. | | | | | | NEW COMMENT 8/13 | | | | | | 2. FABRIC IS TO COMPLY WITH FBC 3105.3.1, NFPA 701. | | | "FIRE RETARDANT FABRIC" IS SPECIFIED IN THE PLANS. | | | PROVIDE TEST REPORT FOR THE PRODUCT PROPOSED. | | | | | | |
|