| Plan Review Notes For Permit 14070321 |
| Permit Number |
14070321 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-05-11 17:07:44 | APPROVED WITH EXCEPTIONS THIS PLAN HAS BEEN APPROVED | | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | | DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL | | | RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF | | | RE-INSPECTION FEE(S). | | | | | | 1) THE FULL BATH ON THE SECOND FLOOR IS NOT PROPERLY | | | VENTED. FBCR P3108.2.1 HORIZONTAL WET VENT. NOT MORE | | | THAN ONE WET- VENTED FIXTURE DRAIN SHALL DISCHARGE | | | UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN CONNECTION. | | | THE TUB DRAIN NEEDS TO DISCHARGE DOWNSTREAM OF THE | | | LAVATORY DRAIN CONNECTION. | | | | | | 2) THE FIRST AND SECOND FLOOR BATHROOM LAVATORIES ARE | | | INCORRECTLY LABELED AS SINKS. IT IS IMPORTANT TO USE | | | THE PROPER NOMENCLATURE BECAUSE THERE IS A DIFFERENCE | | | IN THE REQUIRED TRAP SIZES. PLEASE CORRECT. CITY | | | AMENDMENTS 107.2.1 AND FBCR P3201.7 | | | | | | |
|