| 2015-03-16 12:08:16 | PLAN REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE PLANS THAT WERE SUBMITTED HAVE AN ENGINEER'S |
| | SEAL AND A DIGITAL SIGNATURE. DIGITAL SIGNATURES ARE |
| | ONLY VALID FOR ELECTRONICALLY TRANSMITTED PLANS. PLANS |
| | THAT ARE SUBMITTED ON PAPER ARE REQUIRED TO HAVE THE |
| | ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE ON THEM IN |
| | ADDITION TO THEIR SEAL. FS 471 |
| | |
| | 2) THE TYPE OF CONSTRUCTION AND THE TYPE OF OCCUPANCY |
| | SPECIFIED ON THE COVER SHEET ARE INCORRECT. THE |
| | CONSTRUCTION TYPE SHOULD BE V-B AND THE OCCUPANCY TYPE |
| | IS R-3. |
| | FBC 601 AND 301 |
| | |
| | 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. THE ENGINEER, MANUEL MARTINEZ, IS |
| | THE DESIGNER OF RECORD FOR THIS PROJECT. THE PRODUCT |
| | APPROVALS WERE NOT APPROVED BY ENGINEER. |
| | |
| | 4) DOOR #5 IN THE SCHEDULE ON SHEET 3.0 WHICH SEPARATES |
| | THE GARAGE FROM THE SECOND FLOOR IS REQUIRED TO COMPLY |
| | WITH FBC-R302.5.1 |
| | |
| | 5) SPECIFY WHICH ONE OF THE APPROVED ROOFING ASSEMBLIES |
| | LISTED IN THE PRODUCT APPROVAL FOR GAF MODIFIED ROOFING |
| | SYSTEM (NOA NO. 14-0102.12) WILL BE INSTALLED. IDENTIFY |
| | THE ANCHORING AND DESIGN PRESSURES FOR THE SELECTED |
| | ASSEMBLY. SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117 |
| | CALCULATIONS FOR ENHANCED FASTENING IF THE DESIGN |
| | PRESSURES ARE LESS THAN REQUIRED. |
| | |
| | 6) THE PRODUCT APPROVALS FOR THE OUT-SWING FRENCH DOORS |
| | ( NOA NO. 08-0312.09 ) EXPIRED IN MAY 2011. SUBMIT |
| | CURRENT PRODUCT APPROVALS. DCA RULE 9N-3 |
| | |
| | 7) SUBMIT PRODUCT APPROVALS FOR THE STUCTURAL MULLIONS |
| | THAT WILL BE REQUIRED BETWEEN THE FRENCH DOORS AND THE |
| | FIXED WINDOWS OR SUBMIT PRODUCT APPROVALS FOR FRENCH |
| | DOORS WITH SIDELIGHTS. DCA RULE 9N-3 |
| | |
| | 8) SUBMIT 2 COPIES OF PRODUCT APPROVALS, KEY PLANS AND |
| | INSTALLATION SCHEDULES FOR THE IMPACT PROTECTION |
| | DEVICES THAT ARE REQUIRED FOR THE NON-IMPACT RATED |
| | SLIDING GLASS DOORS (NOA NO. 11-1201.03). DCA RULE 9N-3 |
| | AND FBC 107.2.1 |
| | |
| | 9) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE |
| | SECTIONAL GARAGE DOOR HAS A DESIGN PRESSURE OF -52.0 |
| | PSF AND THE PLANS SEPCIFY THAT -53.2 PSF IS REQUIRED. |
| | FBC 107.2.1 |
| | |
| | 10) THE PLANS SPECIFY SINGLE HUNG WINDOWS AND THE |
| | PRODUCT APPROVAL SUBMITTED IS FOR DOUBLE HUNG WINDOWS. |
| | PLEASE CLARIFY. |
| | |
| | |