| 2014-08-15 17:02:17 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE ENGINEER IS REQUIRED TO SIGN AND SEAL ALL PLAN |
| | SHEETS THAT ARE RELATED TO STRUCTURAL DESIGN. SHEETS |
| | 3.0 AND 4.0 CONTAIN OPENING PRESSURES AND THE COVER |
| | SHEET CONTAINS THE DESIGN COMPLIANCE STATEMENT. CITY |
| | AMENDMENTS 107.1 |
| | |
| | 2) THE OTHER PLAN SHEETS ARE REQUIRED TO HAVE THE NAME |
| | AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. |
| | CITY AMENDMENTS 107.2.1 |
| | |
| | 3) SPECIFY THE TYPE OF CONSTRUCTION AND TYPE OF |
| | OCCUPANCY ON THE PLANS. FBC 602 AND 302 |
| | |
| | 4)THE DESIGN CRITERIA ON SHEETS 7.0 & 8.0 IS INCORRECT. |
| | THE WIND SPEED IS 170 MPH, THE APPLICABLE CODE IS THE |
| | 2010 FBC AND ASCE 7 - 10. |
| | |
| | 5) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY |
| | AMENDMENTS 107.3.4.1 |
| | |
| | 6) THE WINDOW IN THE SECOND FLOOR BATHROOM MARKED (6) |
| | IS NOT LISTED IN THE WINDOW SCHEDULE ON SHEET 3.0. CITY |
| | AMENDMENTS 107.2.1 |
| | |
| | 7) THE BATHROOMS ARE REQUIRED TO COMPLY WITH FBCR 303.3 |
| | FOR NATURAL OR MECHANICAL VENTILATION. |
| | |
| | 8) THE DOORS FROM THE GARAGE TO THE OFFICE (#5) AND |
| | GAME ROOM (#6) ARE REQUIRED TO COMPLY WITH FBCR302.5.1 |
| | OPENING PROTECTION. |
| | |
| | 9) NEITHER THE OFFICE NOR THE GAME ROOM CAN BE USED AS |
| | A SLEEPING ROOM AND SHALL BE SO LABELED ON THE PLANS. |
| | FBCR302.5.1 DOES NOT ALLOW OPENINGS FROM A GARAGE |
| | DIRECTLY INTO A SLEEPING ROOM. |
| | |
| | 10) THE SCOPE OF WORK ON THE COVER SHEET SPECIFIES A |
| | NEW BEDROOM AND FAMILY ROOM ABOVE THE GARAGE. THE |
| | BEDROOM AND FAMILY ROOM ARE NOT LABELED ON THE FLOOR |
| | PLAN. THE ENTIRE SECOND FLOOR IS LABELED GAME ROOM. |
| | PLEASE CORRECT. CITY AMENDMENTS 107.2.1 |
| | |
| | 11) FBCR302.5.1 DOES NOT ALLOW OPENINGS FROM A GARAGE |
| | DIRECTLY INTO A SLEEPING ROOM. SHOW THAT THE SECOND |
| | FLOOR BEDROOM WILL COMPLY. |
| | |
| | 12) SHOW COMPLIANCE WITH FBCR FOR COMPLIANCE WITH FBCR |
| | 314 SMOKE ALARMS AND 315 CARBON MONOXIDE ALARMS. |
| | |
| | 13) SUBMIT TWO SETS OF ENERGY CALCULATIONS. FBC ENERGY |
| | CONSERVATION 103.2.1.1 |
| | |
| | 14) SHOW COMPLIANCE WITH FBCR 806.1 ATTIC VENTILATION. |
| | |
| | 15) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE |
| | EXTERIOR DOORS, SLIDING GLASS DOOR, SECTIONAL GARAGE |
| | DOOR, WINDOWS, ROOF COVERING, BALCONY WATER PROOFING |
| | AND SIMPSON CONNECTORS AS REQUIRED BY DCA RULE 9N-3. |
| | |
| | 16) THE VALUATION FOR THE PROJECT IS LOW. THE ICC |
| | VALUATION IS $155,932.00 FOR A SINGLE FAMILY DWELLING |
| | AND GARAGE. BECAUSE THERE IS NOT A KITCHEN THIS CAN BE |
| | REDUCED TO $135,932.00. CITY AMENDMENTS 109.3 |
| | |
| | 17) IN ORDER TO REDUCE REVIEW TIME, PLEASE SUBMIT A |
| | RESPONSE LETTER INDICATING HOW EACH OF THE PLAN REVIEW |
| | ITEMS HAS BEEN ADDRESSED. |
| | |
| | ROBERT MCDOUGAL |