| Plan Review Notes For Permit 14070263 |
| Permit Number |
14070263 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-07-10 11:14:34 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1. LIFE SAFETY PLAN TO THE OFFICE SPACE NOT PROVIDED. | | | | | | 2. DIMENSIONS AND OCCUPANY LOAD NOT PROVIDED. | | | | | | 3. EXISTING/PROPOSED FIRE ALARM DEVICES NOT PROVIDED. | | | | | | 4. EXISTING/PROPOSED FIRE SPRINKLER NOT PROVIDED. | | | | | | 5. STAIR DETAIL NOT PROVIDED. | | | | | | 6. EXIT SIGNAGE AND EMERGENCY LIGHTING NOT PROVIDED. | | | | | | 7. FIRE EXTINGUISHER LOCATIONS NOT PROVIDED. | | | | | | |
|