| Plan Review Notes For Permit 14070255 |
| Permit Number |
14070255 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-11-05 07:43:33 | 11/5/14 TALKED TO MR. DEXTER. HE SAID HE WILL PROVIDE | | | THE FOLLOWING BEFORE ISSUING THE PERMIT. (ALSO: ADDED | | | $6000 VALUATION FOR WORK IN REAR STUDIO). | | | | | | 1- REVISE ENERGY CALCULATIONS: | | | A) REVISE THE AREA WEIGHTED AVERAGE OVERHANG DEPTH. | | | ACCORDING TO THE PROPERTY APPRAISAL AERIAL VIEW, THERE | | | NO OVERHANGS EXCEPT FOR THE MANSARD IN THE FRONT | | | ELEVATION. SEC. 103.2.2 OF 2010 FBC-ENERGY | | | CONSERVATION. | | | | | | B) REVISE THE TYPE OF ROOF ON PAGE 2 OF 5. COORDINATE | | | WITH ITEM #1 A ABOVE. SEC. 103.2.2 OF 2010 FBC-ENERGY | | | CONSERVATION. | | | | | | 2- PROVIDE MANUFACTURER SPECS FOR THE WINDOWS U-FACTOR | | | AND SHGC FACTOR SPECIFIED IN THE ENERGY CALCULATIONS ON | | | ITEM #7. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. | | | | | | JULIO GOMEZ | | | (561)805-6712 |
|