| Notes |
| Date |
Text |
| 2014-08-01 12:21:06 | RESIDENTIAL (R3) ALTERATION, GAS REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- ENGINEER TO REVISE THE GAS ISOMETRIC: | | | A) CLARIFY/REVISE SIZE OF PIPE AT THE POINT OF DELIVERY | | | (METER). ISOMETRIC CALLS FOR 1/2", WHILE FLOOR PLANS | | | SHOWS 3/4". REVISE AS REQUIRED. SEC. 107.2.1 CITY | | | AMENDMENTS TO FBC. | | | | | | B) GAS ISOMETRIC SHOWN IS BASED ON TABLE 402.4(20). | | | THIS TABLE IS FOR POLYETHYLENE PLASTIC PIPE WITH AN | | | INLET PRESSURE OF 2.0 PSI. GAS ISOMETRIC TO SHOW | | | PRESSURE REGULATORS FOR ALL THE APPLIANCES AS REQUIRED | | | BY SEC. G2421.1(410.1) OF 2010 FBC-RESIDENTIAL. LINE | | | PRESSURE REGULATOR SHALL BE INSTALLED WHERE THE | | | APPLIANCE IS DESIGNED TO OPERATE AT A LOWER PRESSURE | | | THAN THE SUPPLY PRESSURE. | | | | | | ***NOTE: SEPARATE GAS PERMIT IS REQUIRED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|