| 2014-09-04 14:56:42 | DATE: 9/4/2014 | | | PROJECT: ACKER | | | PERMIT#: 14070255 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: PROVISO | | | | | | 1) WHERE INSTALLED IN OR ATTACHED TO A BUILDING OR | | | STRUCTURE, A METAL PIPING SYSTEM(S), INCLUDING GAS | | | PIPING SHALL BE BONDED. .250.104(3)(B) OTHER METAL | | | PIPING. | | | | | | 2) PROVIDE A LIGHTING OUTLET AND SWITCH AT THE ATTIC | | | ACCESS. 210.70(A)(3) | | | | | | 3) CEILING FAN BOXES SHALL COMPLY WITH THE PROVISIONS | | | OF NEC 314.27(D) | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|