Notes
Date Text
2014-07-15 14:32:58THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS.
  
 THE PLAN COLOR LINES WERE VERY LIGHT AND UNREADABLE.
 DARKER LINE ARE REQUIRED.
  
 THE PLAN HAS NO FLOW OR DIRECTION TO THE SHEET
 DRAWINGS. THE RELATION OF EACH SHEET TO THE OVERALL
 PROPOSED CONSTRUCTION IS NOT INDICATED.
  
 THERE ARE NO SYMBOL TABLES IDENTIFING ANY OF THE
 INDICATING LINES.
  
 HIGHLIGHTED AREAS OF GREATER DETAIL ARE NEEDED FOR
 GROUNDING/BONDING LOCATIONS.
  
 THERE IS NO LIFE SAFETY PLAN THAT INDICATES THE IMPACT
 OF THE PROPOSED CONSTRUCTION ON EGRESS/EXITING ROUTES.