| Plan Review Notes For Permit 14070238 |
| Permit Number |
14070238 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-07-21 16:25:24 | | | | *THE COSTRUCTION DOCUMENTS SUBMITTED APPEAR TO BE | | | LAY-OUT SHOP DRAWINGS AND LACK INFORMATION REQUIRED PER | | | 2010 FBC 107.2.1. | | | *THE DRAWINGS DO NOT MEET MINIMUM ELECTRICAL PLAN | | | REVIEW REQUIREMENTS PER 2010 FBC 107.3.5 | | | *PLANS SHALL INCLUDE WIRING METHODS & MATERIALS, BRANCH | | | CIRCUITS, OVERCURRENT PROTECTION, GROUNDING LOAD | | | CALCULATIONS AND AN | | | ELECTRICAL RISER DIAGRAM CONFORMING TO THE 2008 | | | NATIONAL ELECTRICAL CODE. | | | | | | REVIEWED BY K SWIERZKO (561) 805-6700 |
|