Plan Review Notes
Plan Review Notes For Permit 14070238
Permit Number 14070238
Review Stop B
Sequence Number 1
Notes
Date Text
2014-07-14 09:24:33****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE DOCUMENTS SUBMITTED APPEAR TO BE SHOP DRAWINGS
 FOR CONSTRUTION/INSTALLATION. MOST SHEETS HAVE ALL
 INFORMATION GREYED OUT, MAKING THEM DIFFICULT TO READ.
 HOWEVER, THIS INFORMATION CAN BE USED AS SUPPLEMENTAL
 INFORMATION.
  
 PLEASE SEE CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER ONE, SECTION 107.3.5
 WHICH GIVES MINIMUM PLAN REVIEW CRITERIA. PLEASE
 INCLUDE ALL REQUIRED INFORMATION LISTED AS APPLICABLE
 INCLUDING:
  
 107.2.3, MEANS OF EGRESS. PROVIDE A LIFE SAFETY PLAN
 WHICH SHOWS HOW THE PROPOSED IMPROVEMENT WILL AFFECT
 EXITING. SEE FBC CHAPTER 10 INCLUDING FBC 1005 (EGRESS
 WIDTH), FBC 1016 (EXIT ACCESS TRAVEL DISTANCE), ANY
 OTHER INFORMATION TO SHOW CODE COMPLIANCE.
  
 107.3.5.1.1(2) OCCUPANCY GROUP, (3) TYPE OF
 CONSTRUCTION, (6) LIFE SAFETY SYSTEMS, (7) OCCUPANT
 LOAD AND EGRESS INFORMATION, (8) STRUCTURAL
 REQUIREMENTS, (9) MATERIALS PRPOPOSED, (10)
 ACCESSIBILITY INFORMAITON, (11) INTERIOR REQUIREMENTS
 AS APPLICABLE.
  
 2. LIFE SAFETY PLAN TO BE PREPARED BY A DESIGN
 PROFESSIONAL, MOST LIKELY AN ARCHITECT, FS 481.
  
 3. NO STRUCTURAL INFORMATION WAS PROVIDED. AN
 ATTACHMENT DETAIL IS TO BE PROVIDED, FBC 1601.
  
 4. AS THE CONVEYOR BELT APPEARS TO BE ELEVATED, PROVIDE
 A DETAIL SHOWNING COMPLIANCE WITH FBC 2010 ACCESSIBLITY
 307.4.
  