2014-08-12 16:40:29DATE: 8/12/2014
 PROJECT: JEFFERSON AT PALM BEACH LAKES
 PERMIT#: 14070236
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 SHEET E1.61
 1) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT
 SHALL BE CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL.
 EMERGENCY LUMINAIRES THAT OBTAIN POWER FROM A UNIT
 EQUIPMENT AND ARE NOT PART OF THE UNIT EQUIPMENT SHALL
 BE WIRED TO THE UNIT EQUIPMENT AS REQUIRED BY 700.9 AND
 BY ONE OF THE WIRING METHODS OF CHAPTER 3. NEC
 700.12(F) THE CIRCUITING FOR EGRESS ILLUMINATION SHALL
 BE INCLUDED ON THE PLANS.
  
 2) OUTLET BOXES OR OUTLET BOX SYSTEMS USED AS THE SOLE
 SUPPORT OF A CEILING-SUSPENDED (PADDLE) FAN SHALL BE
 LISTED, SHALL BE MARKED BY THEIR MANUFACTURER AS
 SUITABLE FOR THIS PURPOSE, AND SHALL NOT SUPPORT
 CEILING-SUSPENDED (PADDLE) FANS THAT WEIGH MORE THAN 32
 KG (70 LB). FOR OUTLET BOXES OR OUTLET BOX SYSTEMS
 DESIGNED TO SUPPORT CEILING-SUSPENDED (PADDLE) FANS
 THAT WEIGH MORE THAN 16 KG (35 LB), THE REQUIRED
 MARKING SHALL INCLUDE THE MAXIMUM WEIGHT TO BE
 SUPPORTED. NEC314.27(D) INDICATE A NOTE ON THE PLAN FOR
 CEILING FAN BOX SUPPORT.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  