| 2014-07-15 13:55:54 | PLUMBING PLAN REVIEW |
| | PERMIT: 14070211 |
| | ADD: 8100 IBIS BLVD |
| | CONT: HUGHES CONSTRUCTION INDUSTRIES |
| | TEL: (561)792-8004 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE:JULY 15/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) PLANS SUBMITTED ARE SITE PLAN SHOWING THE LOCATION |
| | OF THE PROPOSED (2) GREASE INTERCEPTORS AND SPECS ON A |
| | SCHIER GREAT BASIN 250 GREASE INTERCEPTOR. THERE WAS NO |
| | INFORMATION HOW THESE GREASE INTERCEPTORS WERE SIZED. |
| | 2010 FBC-P 1003.2 APPROVAL. THE SIZE, TYPE AND LOCATION |
| | OF EACH INTERCEPTOR AND OF EACH SEPARATOR SHALL BE |
| | APPROVED BY THE PLUMBING OFFICIAL. THE INTERCEPTOR OR |
| | SEPARATOR SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE |
| | WITH THE MANUFACTURER?S INSTRUCTIONS AND THE |
| | REQUIREMENTS OF THIS SECTION. WASTES THAT DO NOT |
| | REQUIRE TREATMENT OR SEPARATION SHALL NOT BE DISCHARGED |
| | INTO ANY INTERCEPTOR OR SEPARATOR. |
| | |
| | 2) SHOW COMPLIANCE WITH 003.3.1 GREASE INTERCEPTORS AND |
| | AUTOMATIC GREASE REMOVAL DEVICES REQUIRED. |
| | A GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE |
| | SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES |
| | AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD |
| | PREPARATION AREAS, SUCH AS IN RESTAURANTS, HOTEL |
| | KITCHENS, HOSPITALS, SCHOOL KITCHENS, BARS, FACTORY |
| | CAFETERIAS AND CLUBS. FIXTURES AND EQUIPMENT SHALL |
| | INCLUDE POT SINKS, PRERINSE SINKS; SOUP KETTLES OR |
| | SIMILAR DEVICES;WOK STATIONS; FLOOR DRAINS OR SINKS |
| | INTO WHICH KETTLES ARE DRAINED; AUTOMATIC HOOD WASH |
| | UNITS AND DISHWASHERS WITHOUT PRERINSE SINKS.GREASE |
| | INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL |
| | RECEIVE WASTE ONLY FROM FIXTURES AND EQUIPMENT THAT |
| | ALLOW FATS, OILS OR GREASE TO BE DISCHARGED. |
| | |
| | 3) SHOW HOW THE GREASE INTERCEPTOR WAS SIZED AND IN |
| | COMPLIANCE WITH: |
| | 2010 FBC-P 1003.3.4 GREASE INTERCEPTORS AND AUTOMATIC |
| | GREASE REMOVAL DEVICES. |
| | GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL |
| | DEVICES SHALL BE SIZED IN ACCORDANCE WITH PDI G101, |
| | ASME A112.14.3 APPENDIX A, OR ASME A112.14.4. GREASE |
| | INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL |
| | BE DESIGNED AND TESTED IN ACCORDANCE WITH PDI G101, |
| | ASME A112.14.3 OR ASME A112.14.4. GREASE INTERCEPTORS |
| | AND AUTOMATIC GREASE REMOVAL DEVICES SHALL BE INSTALLED |
| | IN ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS. |
| | |
| | ALL GREASE INTERCEPTORS TO VERIFY COMPLIANCE WITH THE |
| | CITY?S MUNI CODE SEC. 90-126. PROHIBITIONS AND |
| | LIMITATIONS OF DISCHARGE.(7) MINERAL OIL IN EXCESS OF |
| | 50 MG/L OR ANIMAL/VEGETABLE FATS, WAX, GREASE, OR OILS |
| | IN EXCESS OF 100 MG/L, WHETHER EMULSIFIED OR NOT; OR |
| | SUBSTANCES WHICH MAY SOLIDIFY OR BECOME VISCOUS AT |
| | TEMPERATURES LOWER THAN OR EQUAL TO 150 DEGREES |
| | FAHRENHEIT (65.56 DEGREES CELSIUS). |
| | |
| | IF THIS AMOUNT OF FATS, OILS OR GREASE IS EXCEEDED THE |
| | REQUIRED MAINTENANCE & CLEANOUT SCHEDULE WILL BE |
| | INCREASED TO KEEP IN COMPLIANCE WITH THE CITY'S |
| | MUNICIPAL CODE OF ORDINANCES. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | 7/18/2014 JULIAN BLAZER CALLED (THE WEITZ CO |
| | REPRESENTATIVE) IN REFERANCE TO THIS PERMIT. IN |
| | REVIEWING THE APPROVED PLANS SHEET PL003 THE GREASE |
| | TRAP IS SIZED USING THE 2010 FBC-P TABLE 1003.5.1 WHICH |
| | IS FOR CONCRETE VAULT TYPE INTERCEPTORS. THE SUBMITTED |
| | PRODUCT IS SCHIER (2) GB-250 TYPE HYDROMECHANICAL |
| | GREASE INTERCEPRTORS, NOT THE TYPE OF INTERCEPTOR THE |
| | DESIGNER OF RECORD REQUIRES ,NOR HAS APPROVED WITH |
| | THEIR SHOP DRAWING STAMP OF APPROVAL. |
| | |
| | PLEASE NOTE A REVISION WILL BE NEEDED TO THE PLAN SINCE |
| | THE FORMULA AND SIZING ON PL003 IS FOR A CONCRETE VAULT |
| | TYPE INTERCEPTOR. 2ND THE SCHIER GREASE INTERCEPTOR |
| | WILL NEED TO BE SIZED USING THIER OWN FORMULA FOR |
| | GREASE REMOVAL & RETENTION, REVIEWED BY THE DESIGNER OF |
| | RECORD, AND SHOP DRAWING STAMP OF APPROVAL ON THE |
| | DOCUMENTS. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |