| 2014-07-18 12:14:29 | DATE: 7/18/2014 | | | PROJECT: FIRE ALARM FOR NEW BUILDOUT 400 N. CONGRESS. | | | PERMIT#: 14070166 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | 1) REVISE THE NAC POWER SUPPLY CALCULATIONS INDICATING | | | CAPACITY TO SUPPORT THE ADDITIONAL LOAD. SHOW THE | | | EXISTING DEVICE LOAD AND THE NEW LOAD ADDED FROM THE | | | NEW DEVICES. | | | | | | 2) REVISE THE RISER TO MATCH THE NAC POWER SUPPLY | | | CALCULATIONS AND THE FLOOR PLAN. THE FLOOR PLAN | | | CURRENTLY INDICATES 7 NEW NAC DEVICES AND ONE | | | INITIATING DEVICE. THE RISER INDICATESA TOTAL OF 14 NEW | | | DEVICES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT | | | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM | | | ITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND | | | LEAVE THE PREVIOUSLY REVIEWED SHEETS. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|