| Plan Review Notes For Permit 14070159 |
| Permit Number |
14070159 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-07-10 09:42:34 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. FOR THE ACCORDION SHUTTER, SPECIFY FASTENER AS PER | | | ANCHOR SCHEDULE ON SHEET 11. CONTRACTOR HAS SPECIFIED | | | "2 1/4 ELCO TAPCON." THIS IS NOT AN OPTION; ELCO IS A | | | BRAND AND TAPCON IS ANOTHER BRAND. THERE ARE TWO | | | DIFFERENT TYPES OF TAPCONS AND TWO DIFFERENT ELCO | | | ULTRACONS ON THE CHART (DIFFERENT DIAMETER). ANCHOR | | | SPACING PROPOSED DOES NOT COMPLY FOR ANY OF THE | | | FASTENER OPTIONS. | | | | | | PLEASES REVISE THE FASTENER PROPOSED AND ANCHOR SPACING | | | ACCORDINGLY. | | | | | | |
|