| 2014-07-07 16:58:37 | RE-ROOF BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- TAS 105 FASTENER WITHDRAWAL TEST REPORT SUBMITTED: |
| | A) ROOF SKETCH SUBMITTED DOESN'T MATCH ACTUAL ROOF DECK |
| | SHOWN ON THE PROPERTY APPRAISAL WEBSITE. REVISE AS |
| | REQUIRED. SEC. 107.2.1 CITY AMENDMENTS TO FBC AND SEC. |
| | 10.1.9 OF TAS 105-11. |
| | |
| | B) NEED AT LEAST 3 TESTS TO BE PERFORMED IN THE CORNER |
| | AREA AS REQUIRED BY SEC. 8.1 OF TAS 105-11. THE FIELD |
| | WITHDRAWAL RESISTANCE TEST RECORDING SHEET SHOWS ONLY |
| | TWO TEST DONE IN THE CORNER AREA. BUT, THE ROOF SKETCH |
| | SHOWING THE TEST LOCATIONS ONLY SHOW ONE TEST IN THE |
| | CORNER AREA (TEST T-2). ALSO, TEST #4 IS NOT IN A |
| | CORNER AREA. REVISE EVERYTHING AS REQUIRED TO MATCH. |
| | |
| | C) IF MORE THAN 25% OF THE ROOF SYSTEM IS TO BE |
| | RE-ROOF, THEN, ENTIRE ROOF NEEDS TO BE RE-ROOFED. SEC. |
| | 611.1.1 OF 2010 FBC-EXISTING BUILDING CODE. ALSO, |
| | NUMBER OF PULL OUT TEST SHALL BE CONDUCTED ACCORDINGLY. |
| | SEC. 8 OF TAS 105-11. |
| | |
| | D) CONTRACTOR SPECIFIED ON PERMIT APPLICATION RE-ROOF |
| | WITH TAMKO PONDING WATER SPECS. TEST NEED TO IDENTIFY |
| | THE PONDING WATER LOCATIONS AS REQUIRED BY SEC. 8.4 OF |
| | TAS 105-11. |
| | |
| | 2) TAS 105 REPORT SHOWS AREAS WERE THE ROOF DECK IS |
| | BAD. NEED STRUCTURAL SUB-PERMIT TO PERFORM THE DECK |
| | REPAIRS. PROVIDE COMPLETE DETAILS/ SPECIFICATIONS FOR |
| | DECK REPAIRS. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| | CONTRACTOR DOING THE DECK REPAIRS TO HAVE PROPER |
| | LICENSE AS REQUIRED BY SEC. 489.113 FLORIDA STATUTES. |
| | |
| | 3- RAS 117 CALCULATIONS SUBMITTED: ENGINEER TO REVISE |
| | THE SPACING OF THE NAILS AT THE SIDE LAP. NEED TO MATCH |
| | THE SPACING SHOWING ON OPTION #3 OF PAGE 11 OF THE NOA |
| | 12-0716.14 SUBMITTED. REVISE CALCULATIONS ACCORDINGLY. |
| | THIS IS REQUIRED BY SEC. 8.1 OF RAS 117. |
| | |
| | 4- ROOF NEEDS POSITIVE DRAINAGE AS REQUIRED BY |
| | EXCEPTION ON SEC. 611.1 OF 2010 FBC-EXISTING BUILDING |
| | CODE. |
| | |
| | ***NOTES: |
| | **** MOISTURE SURVEY TEST MAY BE REQUIRED. SEE ITEM |
| | 1(D) ABOVE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |