| 2014-09-16 11:24:11 | MECHANICAL REVIEW APPROVED WITH PROVISO: |
| | |
| | 1- EQUIPMENT SIZING CALCULATIONS SUBMITTED: |
| | A) NEED TO COORDINATE THE EQUIPMENT SIZING CALCULATIONS |
| | WITH THE ENERGY CALCULATIONS. SEC. 103.2.2 OF 2010 |
| | FBC-ENERGY CONSERVATION. |
| | REVISE AS REQUIRED TO MATCH THE WINDOWS/DOORS U-FACTOR |
| | AND SHGC FACTOR, THE CEILING INSULATION R-VALUE, ETC. |
| | |
| | B) CALCULATIONS ARE TAKING INTO CONSIDERATION 62 |
| | PEOPLE. THIS IS A SINGLE FAMILY RESIDENCE. THERE ARE |
| | NOT 62 PEOPLE TO BE CONSIDERED FOR EQUIPMENT SIZING |
| | CALCULATIONS. REVISE AS REQUIRED. SEC. 403.6.1 OF 2010 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | C) THE LATENT CAPACITY OF THE EQUIPMENT SHALL NOT BE |
| | LESS THAN THE CALCULATED LATENT LOAD. REVISE EQUIPMENT |
| | FOR SYSTEM 1 AS REQUIRED. SEC. 403.6.1.1 OF 2010 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | 2- A/C PLAN SUBMITTED: |
| | A) REVISE EQUIPMENT LISTED IN THE A/C PLAN TO MATCH |
| | EQUIPMENT LISTED IN THE REVISED EQUIPMENT SIZING |
| | CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| | CONSERVATION. THE GARAGE EQUIPMENT SHOWN ON A/C PLAN |
| | DOESN'T MATCH THE ONE SHOWN ON THE EQUIPMENT SIZING |
| | CALCULATIONS. |
| | |
| | B) REVISE GENERAL MECHANICAL NOTE #6: THE MINIMUM DOOR |
| | UNDERCUT IS NOT 3/4". SEE SEC. M1602.4 OF 2010 |
| | FBC-RESIDENTIAL AND REVISE ORIGINAL NOTE AS REQUIRED. |
| | |
| | C) YOGA ROOM DOESN'T HAVE BALANCED RETURN AIR. SEC. |
| | M1602.4 OF 2010 FBC-RESIDENTIAL. REVISE ORIGINAL |
| | DRAWING TO INCLUDE THE RETURN AIR GRILL. |
| | |