2014-09-15 12:43:09NEW SINGLE FAMILY RESIDENCE (R3) SECOND MECHANICAL
 REVIEW CHECKLIST
 CODE: 2010 FBC.
  
  
 1-EQUIPMENT SIZING CALCULATIONS SUBMITTED:
 A) NEED TO COORDINATE THE EQUIPMENT SIZING CALCULATIONS
 WITH THE ENERGY CALCULATIONS. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
 REVISE AS REQUIRED TO MATCH THE WINDOWS/DOORS U-FACTOR
 AND SHGC FACTOR, THE CEILING INSULATION R-VALUE, ETC.
  
 B) CALCULATIONS ARE TAKING INTO CONSIDERATION 62
 PEOPLE. THIS IS A SINGLE FAMILY RESIDENCE. THERE ARE
 NOT 62 PEOPLE TO BE CONSIDERED FOR EQUIPMENT SIZING
 CALCULATIONS. REVISE AS REQUIRED. SEC. 403.6.1 OF 2010
 FBC-ENERGY CONSERVATION.
  
 C) THE LATENT CAPACITY OF THE EQUIPMENT SHALL NOT BE
 LESS THAN THE CALCULATED LATENT LOAD. REVISE EQUIPMENT
 FOR SYSTEM 1 AS REQUIRED. SEC. 403.6.1.1 OF 2010
 FBC-ENERGY CONSERVATION.
  
 2- A/C PLAN SUBMITTED:
 A) REVISE EQUIPMENT LISTED IN THE A/C PLAN TO MATCH
 EQUIPMENT LISTED IN THE REVISED EQUIPMENT SIZING
 CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION. THE GARAGE EQUIPMENT SHOWN ON A/C PLAN
 DOESN'T MATCH THE ONE SHOWN ON THE EQUIPMENT SIZING
 CALCULATIONS.
  
 B) REVISE GENERAL MECHANICAL NOTE #6: THE MINIMUM DOOR
 UNDERCUT IS NOT 3/4". SEE SEC. M1602.4 OF 2010
 FBC-RESIDENTIAL AND REVISE ORIGINAL NOTE AS REQUIRED.
  
 C) YOGA ROOM DOESN'T HAVE BALANCED RETURN AIR. SEC.
 M1602.4 OF 2010 FBC-RESIDENTIAL. REVISE ORIGINAL
 DRAWING TO INCLUDE THE RETURN AIR GRILL.
  