2014-09-12 14:35:33NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 CHECKLIST
 CODE: 2010 FBC.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ENTRY DOORS AS SHOWN ON PLANS.
  
 B) CABANA EXTERIOR DOOR AS SHOWN ON PLANS.
  
 C) ARCHED FIXED WINDOW 5'-0" X 6'-6" IN GARAGE AS SHOWN
 ON PLANS.
  
 D) SLIDING GLASS DOORS. NOA 11-1018.14 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. NEED CURRENT NOA.
  
 E) 9'-0" WIDE OVERHEAD GARAGE DOORS AS SHOWN ON PLANS.
 NOA SUBMITTED IS FOR 16'-2" DOORS.
  
 F) ROOF TILE. PROVIDE CURRENT REVISED FLORIDA PRODUCT
 APPROVAL FL3505-R6 AND REVISED ESR 1775. ONE SUBMITTED
 IS FL3506-R5.
  
 2- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 OF CITY
 AMENDMENTS TO FBC.
  
 3- A) WINDOWS FOR BEDROOM #3 AND #4 DON'T COMPLY WITH
 THE EGRESS REQUIREMENTS OF SEC. R310 OF 2010
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 B) PROVIDE MANUFACTURER'S CUT SHEETS FOR BEDROOM #3 AND
 #4 WINDOW SIZE TO VERIFY COMPLIANCE WITH ALL THE
 MINIMUM OPENINGS REQUIRED BY SEC. R310 OF 2010
 FBC-RESIDENTIAL (NEED TO VERIFY MIN. CLEAR WIDTH, MIN.
 CLEAR HEIGHT AND TOTAL MIN. CLEAR AREA).
  
 4- PROVIDE MANUFACTURER'S SPECS FOR FOAM OUTRIGGERS
 SHOWN ON ELEVATIONS AND WALL SECTIONS TO VERIFY
 COMPLIANCE WITH SEC. R316 OF 2010 FBC-RESIDENTIAL.
  
 5- CLARIFY BLOCKED DIAPHRAGM ROOF ON SHEET S203. IT'S
 NOT CLEAR IS USING RING SHANK NAILS OR NOT. SEC.
 R803.2.3.1 REQUIRES RING SHANK NAILS.
  
 6- PROVIDE COMPLETE SPECIFICATIONS FOR GARAGE DOOR
 #1119 TO VERIFY COMPLIANCE WITH SEC. R302.5.1 OF 2010
 FBC-RESIDENTIAL.
  
 7- REVISE ENERGY CALCULATIONS (SEC. 103.2.1.1.2 OF 2010
 FBC-ENERGY CONSERVATION):
 A) PROVIDE THE JURISDICTION NUMBER ON TOP OF FORM
 B) REVISE DOORS INFORMATION ON PAGE 3 OF 6. SEE PLANS
 AND PRODUCT APPROVALS SUBMITTED. SEE SEC. 405.5.3 OF
 2010 FBC-ENERGY CONSERVATION TO SEE HOW TO CALCULATED
 DOOR WITH GLAZING.
 C) COORDINATE COOLING AND HEATING INFORMATION WITH THE
 A/C EQUIPMENT SIZING CALCULATIONS SUBMITTED. ALSO,
 INCLUDE THE UNIT LOCATED IN THE GARAGE.
  
 *****NOTES:
 * PLEASE PROVIDE A RESPONSE LETTER CLEARLY ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ** PLEASE REPLACE EACH REVISED SHEET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved