| 2014-09-12 14:35:33 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW |
| | CHECKLIST |
| | CODE: 2010 FBC. |
| | |
| | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) ENTRY DOORS AS SHOWN ON PLANS. |
| | |
| | B) CABANA EXTERIOR DOOR AS SHOWN ON PLANS. |
| | |
| | C) ARCHED FIXED WINDOW 5'-0" X 6'-6" IN GARAGE AS SHOWN |
| | ON PLANS. |
| | |
| | D) SLIDING GLASS DOORS. NOA 11-1018.14 SUBMITTED WAS |
| | SUPERSEDED BY MIAMI-DADE. NEED CURRENT NOA. |
| | |
| | E) 9'-0" WIDE OVERHEAD GARAGE DOORS AS SHOWN ON PLANS. |
| | NOA SUBMITTED IS FOR 16'-2" DOORS. |
| | |
| | F) ROOF TILE. PROVIDE CURRENT REVISED FLORIDA PRODUCT |
| | APPROVAL FL3505-R6 AND REVISED ESR 1775. ONE SUBMITTED |
| | IS FL3506-R5. |
| | |
| | 2- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT |
| | APPROVALS AS REQUIRED BY SEC. 107.3.4.1 OF CITY |
| | AMENDMENTS TO FBC. |
| | |
| | 3- A) WINDOWS FOR BEDROOM #3 AND #4 DON'T COMPLY WITH |
| | THE EGRESS REQUIREMENTS OF SEC. R310 OF 2010 |
| | FBC-RESIDENTIAL. REVISE AS REQUIRED. |
| | |
| | B) PROVIDE MANUFACTURER'S CUT SHEETS FOR BEDROOM #3 AND |
| | #4 WINDOW SIZE TO VERIFY COMPLIANCE WITH ALL THE |
| | MINIMUM OPENINGS REQUIRED BY SEC. R310 OF 2010 |
| | FBC-RESIDENTIAL (NEED TO VERIFY MIN. CLEAR WIDTH, MIN. |
| | CLEAR HEIGHT AND TOTAL MIN. CLEAR AREA). |
| | |
| | 4- PROVIDE MANUFACTURER'S SPECS FOR FOAM OUTRIGGERS |
| | SHOWN ON ELEVATIONS AND WALL SECTIONS TO VERIFY |
| | COMPLIANCE WITH SEC. R316 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 5- CLARIFY BLOCKED DIAPHRAGM ROOF ON SHEET S203. IT'S |
| | NOT CLEAR IS USING RING SHANK NAILS OR NOT. SEC. |
| | R803.2.3.1 REQUIRES RING SHANK NAILS. |
| | |
| | 6- PROVIDE COMPLETE SPECIFICATIONS FOR GARAGE DOOR |
| | #1119 TO VERIFY COMPLIANCE WITH SEC. R302.5.1 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | 7- REVISE ENERGY CALCULATIONS (SEC. 103.2.1.1.2 OF 2010 |
| | FBC-ENERGY CONSERVATION): |
| | A) PROVIDE THE JURISDICTION NUMBER ON TOP OF FORM |
| | B) REVISE DOORS INFORMATION ON PAGE 3 OF 6. SEE PLANS |
| | AND PRODUCT APPROVALS SUBMITTED. SEE SEC. 405.5.3 OF |
| | 2010 FBC-ENERGY CONSERVATION TO SEE HOW TO CALCULATED |
| | DOOR WITH GLAZING. |
| | C) COORDINATE COOLING AND HEATING INFORMATION WITH THE |
| | A/C EQUIPMENT SIZING CALCULATIONS SUBMITTED. ALSO, |
| | INCLUDE THE UNIT LOCATED IN THE GARAGE. |
| | |
| | *****NOTES: |
| | * PLEASE PROVIDE A RESPONSE LETTER CLEARLY ADDRESSING |
| | EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ** PLEASE REPLACE EACH REVISED SHEET. |
| | |