| 2014-07-30 10:56:02 | NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- PROVIDE THE NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE A/C DESIGN AS REQUIRED BY SEC. | | | 107.2.1 OF CITY AMENDMENTS TO FBC. | | | | | | 2- EQUIPMENT CALCULATIONS SUBMITTED: SELECTED EQUIPMENT | | | FOR SYSTEM #1 AND SYSTEM #2 DON'T COMPLY WITH SEC. | | | 403.6.1.1 OF 2010 FBC-ENERGY CONSERVATION. SELECTED | | | EQUIPMENT EXCEEDS THE 1.15 TIMES GREATER THAN THE TOTAL | | | LOAD CALCULATED. REVISE AS REQUIRED. | | | | | | 3- A/C PLAN SUBMITTED: | | | A) REVISE EQUIPMENT LISTED IN THE A/C PLAN TO MATCH | | | EQUIPMENT LISTED IN THE REVISED EQUIPMENT SIZING | | | CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY | | | CONSERVATION. | | | | | | B) GARAGE EQUIPMENT LISTED IN THE A/C PLAN TO MATCH | | | EQUIPMENT LISTED IN THE EQUIPMENT SIZING CALCULATIONS. | | | SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. | | | | | | C) REVISE GENERAL MECHANICAL NOTE #6: THE MINIMUM DOOR | | | UNDERCUT IS NOT 3/4". SEE SEC. M1602.4 OF 2010 | | | FBC-RESIDENTIAL AND REVISE AS REQUIRED. | | | | | | D) YOGA ROOM DOESN'T HAVE BALANCED RETURN AIR. SEC. | | | M1602.4 OF 2010 FBC-RESIDENTIAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected]. | | | | | | |
|