2014-07-30 10:56:02NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE A/C DESIGN AS REQUIRED BY SEC.
 107.2.1 OF CITY AMENDMENTS TO FBC.
  
 2- EQUIPMENT CALCULATIONS SUBMITTED: SELECTED EQUIPMENT
 FOR SYSTEM #1 AND SYSTEM #2 DON'T COMPLY WITH SEC.
 403.6.1.1 OF 2010 FBC-ENERGY CONSERVATION. SELECTED
 EQUIPMENT EXCEEDS THE 1.15 TIMES GREATER THAN THE TOTAL
 LOAD CALCULATED. REVISE AS REQUIRED.
  
 3- A/C PLAN SUBMITTED:
 A) REVISE EQUIPMENT LISTED IN THE A/C PLAN TO MATCH
 EQUIPMENT LISTED IN THE REVISED EQUIPMENT SIZING
 CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 B) GARAGE EQUIPMENT LISTED IN THE A/C PLAN TO MATCH
 EQUIPMENT LISTED IN THE EQUIPMENT SIZING CALCULATIONS.
 SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 C) REVISE GENERAL MECHANICAL NOTE #6: THE MINIMUM DOOR
 UNDERCUT IS NOT 3/4". SEE SEC. M1602.4 OF 2010
 FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 D) YOGA ROOM DOESN'T HAVE BALANCED RETURN AIR. SEC.
 M1602.4 OF 2010 FBC-RESIDENTIAL.
  