2014-07-29 14:34:07NEW SINGLE FAMILY RESIDENCE(R3) BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1-BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED LAND
 DEVELOPMENT CODE.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ALL EXTERIOR DOORS, INCLUDING THE ARCHED ENTRY DOOR
 WITH SIZE AS SHOWN ON PLANS.
 B) ALL WINDOW TYPES SHOWN ON PLANS.
 C) WINDOW AND DOOR MULLIONS. *****NOTE: CLEARLY SPECIFY
 MULLION SIZE AND FASTENING TO VERIFY COMPLIANCE WITH
 THE DESIGN PRESSURES.
 D) ROOF TILE.
 E) ROOF TILE ADHESIVE (IF SPECIFIED BY THE DESIGNER OF
 RECORD). COORDINATE WITH ADHESIVES LISTED IN TILE
 PRODUCT APPROVAL.
 F) FLAT ROOF. IDENTIFY APPROVED ASSEMBLY TO BE
 INSTALLED AND PROVIDE RAS 117 CALCULATIONS IF REQUIRED.
 G) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS.
 H) GARAGE DOORS.
 I) PRECAST LINTELS AS SPECIFIED ON PLANS.
 J) "PHANTOM SCREEN" SHOWN ON FLOOR PLAN AND BUILDING
 SECTION A-A. ***NOTE: PROVIDE KEY PLAN AND COMPLETE
 INSTALLATION SCHEDULE. SEC. 107.2.1 CITY AMENDMENTS TO
 FBC.
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
  
 4- A) WINDOWS FOR BEDROOM #2 AND #3 DON'T COMPLY WITH
 THE EGRESS REQUIREMENTS OF SEC. R310 OF 2010
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 B) PROVIDE MANUFACTURER'S CUT SHEETS FOR BEDROOM #2
 WINDOW SIZE TO VERIFY COMPLIANCE WITH ALL THE MINIMUM
 OPENINGS REQUIRED BY SEC. R310 OF 2010 FBC-RESIDENTIAL
 (NEED TO VERIFY MIN. CLEAR WIDTH, MIN. CLEAR HEIGHT AND
 TOTAL MIN. CLEAR AREA).
  
 5- ALL DRAWINGS NEED TO HAVE THE ARCHITECT'S ORIGINAL
 SIGNATURE AS REQUIRED BY CHAPTER 481 FLORIDA STATUTES.
 SIGNATURE STAMP IS NOT ALLOWED.
  
 6- PROVIDE MANUFACTURER'S SPECS FOR BBQ GRILL DESIGNED
 TO BE INSTALLED IN PORCH AS SHOWN ON PLANS. SEC.
 G2408.1 OF 2010 FBC-RESIDENTIAL.
  
 7- PROVIDE SOIL TEST REPORT (2 COPIES). SEC. R401.4 OF
 2010 FBC-RESIDENTIAL.
  
 8- PROVIDE DRAINAGE PLAN. SEC. R401.3 OF 2010
 FBC-RESIDENTIAL.
  
 9- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION FOR THE NEW BUILDING WAS UPDATED TO
 $627,910 AS REQUIRED BY SEC. 109.3 CITY AMENDMENTS TO
 FBC. THE PERMIT FEE BALANCE IS $10,797.14.
  
 10- SHEET A201: SPECIFY ATTIC ACCESS SIZE FOR ATTIC
 ACCESS SHOWN IN GARAGE. SEC. R807 OF 2010
 FBC-RESIDENTIAL.
  
 11- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 INSTALLATION OF THE 48" H. METAL DEC. FINIAL SHOWN ON
 THE ELEVATIONS. SEC. R301.1 OF 2010 FBC-RESIDENTIAL.
  
 12- DESIGNER OF RECORD TO PROVIDE COMPLETE ROOF TILE
 FASTENING SPECIFICATIONS AS REQUIRED BY SEC. 107.2.1.2
 CITY AMENDMENTS TO FBC. IF USING NAILS OR SCREWS, THEN
 SPECIFY SIZE AND NUMBER OF NAILS/SCREWS PER TILE.
 COORDINATE INFORMATION WITH WALL SECTION IN SHEET A801.
  
 13- WALL SECTION ON SHEET A801: COORDINATE INFORMATION
 SHOWN ON PLANS WITH INFORMATION SHOWN ON THE ENERGY
 CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION. FOR EXAMPLE CHECK ROOF TYPE OF INSULATION
 (BATT INSULATION OR ICYNENE INSULATION), VENTED OR
 UNVENTED ATTIC, ETC. REVISE AS REQUIRED TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
 ***NOTE: CHECK ICYNENE ICC REPORT FOR LIMITATIONS ON
 MAX. THICKNESSS AND R-VALUE.
  
 14- PROVIDE MANUFACTURER'S SPECS FOR FOAM OUTRIGGERS
 SHOWN ON ELEVATIONS AND WALL SECTIONS TO VERIFY
 COMPLIANCE WITH SEC. R316 OF 2010 FBC-RESIDENTIAL.
 ***NOTE: CLARIFY IF USING WOOD OUTRIGGERS OR FOAM
 OUTRIGGERS KEY NOTES ON SHEET A301 CALLS FOR WOOD,
 WHILE ELEVATIONS AND WALL SECTION CALL FOR FOAM. REVISE
 AS REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS TO
 FBC.
  
 15- PROVIDE EVALUATION REPORT FOR THE ICYNENE
 INSULATION TO VERIFY COMPLIANCE WITH SEC. R316 OF 2010
 FBC-RESIDENTIAL. ***NOTE: SEE LIMITATIONS FOR MAXIMUM
 THICKNES AND R-VALUE. COORDINATE WITH ENERGY
 CALCULATIONS.
  
 16- SHEET A801: REVISE ALL THE WINDOWS AND DOORS
 STRUCTURAL BUCK DETAILS. BUCK NEEDS TO PROVIDE FULL
 SUPPORT TO THE DOOR AND WINDOW FRAME AS REQUIRED BY
 SEC. R612.10.2 OF 2010 FBC-RESIDENTIAL.
  
 17- ENERGY CALCULATIONS ARE TAKING THE CEILING FAN
 CREDIT. PROVIDE PLANS SHOWING NUMBER OF CEILING FANS
 AND SIZES IN ALL ROOMS AS REQUIRED BY SEC. 405.6.6 AND
 TABLE 405.6.6 OF 2010 FBC-ENERGY CONSERVATION.
  
 18- SHEET S203: REVISE THE "BLOCKED DIAPHRAGM ROOF".
 NEED TO SPECIFY RING SHANK NAILS AS REQUIRED BY SEC.
 R803.2.3.1 OF 2010 FBC-RESIDENTIAL. ALSO, SPECIFY ROOF
 NAILING SPACING FOR ROOF ZONE #3. OTHERWISE, PROVIDE
 CALCULATIONS SHOWING THAT THE SPECIFIED NAILS WILL HAVE
 THE SAME OR BETTER VALUE THAN THE RING SHANK NAILS.
 SEC. 107.2.1.3 OF CITY AMENDMENTS TO FBC.
  
 19- PROVIDE COMPLETE SPECIFICATIONS FOR GARAGE DOOR
 #1119 TO VERIFY COMPLIANCE WITH SEC. R302.5.1 OF 2010
 FBC-RESIDENTIAL.
  
 20- REVISE ENERGY CALCULATIONS (SEC. 103.2.1.1.2 OF
 2010 FBC-ENERGY CONSERVATION):
 A) NUMBER OF BEDROOMS IS INCORRECT. SEE PLANS.
 B) REVISE NAME OF BUILDER AND PROVIDE THE JURISDICTION
 NUMBER ON TOP OF FORM
 C) CLARIFY IF VENTED OR UNVENTED ATTIC. SEE PLANS.
 D) CLARIFY DOORS INFORMATION ON PAGE 3 OF 6: WHERE ARE
 THE INSULATED AND WOOD DOORS LOCATED ON PLANS? ALSO,
 COORDINATE WITH THE PRODUCT APPROVALS. CLARIFY DOOR
 WIDTH, DOOR HEIGHT AND DOOR AREA SHOWN.
 E) CLARIFY WINDOWS INFORMATION ON PAGE 4 OF 6: CLARIFY
 THE OVERHANG SEPARATION SHOWN . SEE PLANS.
 F) COORDINATE COOLING AND HEATING INFORMATION WITH THE
 A/C EQUIPMENT SIZING CALCULATIONS SUBMITTED. ALSO,
 INCLUDE THE UNIT LOCATED IN THE GARAGE.
  
 21- SHEET A901:
 A) REVISE ALL WINDOWS AND DOORS BUCK DETAILS. SEC.
 R612.10.2 OF 2010 FBC-RESIDENTIAL. COORDINATE WITH ITEM
 #16 ABOVE.
 B) UPDATE THE EXTERIOR WINDOW & DOOR GENERAL NOTES:
 (1)REVISE THE WIND LOAD. SPECIFY THE ULTIMATE AND
 NOMINAL WIND LOADS. SEC. R301.2.1.3 OF 2010
 FBC-RESIDENTIAL. (2)UPDATE BUILDING CODE CITED.
  
 *****NOTES:
 * PLEASE PROVIDE A RESPONSE LETTER CLEARLY ADDRESSING
 EACH COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ** PLEASE REPLACE EACH REVISED SHEET.
  