| 2014-07-10 07:17:08 | 1ST REVIEW: 2010 FBC | | | | | | THE APPLICANT HAS USED THE DESIGN GUIDE BELOW. | | | | | | FBC-R301.2.1.1.1 DESIGN. | | | THE FOLLOWING DESIGN GUIDE SHALL BE ACCEPTED AS | | | CONFORMING TO ACCEPTED ENGINEERING PRACTICES: AAF GUIDE | | | TO ALUMINUM CONSTRUCTION IN HIGH-WIND AREAS. VINYL AND | | | ACRYLIC PANELS SHALL BE REMOVABLE. REMOVABLE PANELS | | | SHALL BE IDENTIFIED AS REMOVABLE BY A DECAL. THE | | | IDENTIFICATION DECAL SHALL ESSENTIALLY STATE: | | | ?REMOVABLE PANEL SHALL BE REMOVED WHEN WIND SPEEDS | | | EXCEED 75 MPH (34 M/S).? DECALS SHALL BE PLACED SUCH | | | THAT THE DECAL IS VISIBLE WHEN THE PANEL IS INSTALLED. | | | | | | PLEASE EXPLAIN HOW YOU CAN HAVE TWO SHEETS FROM THE | | | REFERENCED MANUAL WITH IDENTICAL PAGE NUMBERS AND | | | EDITIONS, BUT DIFFERENT DETAILS. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|