| 2014-07-25 09:15:02 | DATE: 7/25/2014 |
| | PROJECT: 224 LAKEWOOD RD. |
| | PERMIT#: 14070012 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) THERE IS AN ELECTRICAL PERMIT APPLICATION INCLUDED |
| | WITH THIS SUBMITTAL PACKAGE HOWEVER THERE ARE NO |
| | ELECTRICAL PLANS OR SPECIFICATIONS INCLUDED AS REQUIRED |
| | FOR REVIEW. PROVIDE COMPLETE PLANS AND SPECIFICATIONS |
| | TO INCLUDE THE FOLLOWING: FBC WPB AMENDMENTS, SECTION |
| | 107.2.1 |
| | 1. A DETAILED SCOPE OF ELECTRICAL WORK TO BE PERFORMED. |
| | 2. A FLOOR PLAN INDICATING THE LOCATION OF THE |
| | ELECTRICAL PANEL AND ALL THE ITEMS AS IDENTIFIED ON THE |
| | SCOPE OF WORK. |
| | 3. A ONE LINE RISER DIAGRAM OF THE ELECTRICAL SERVICE |
| | IF ONE IS TO BE INCLUDED. |
| | 4. A COMPLETE LOAD SUMMARY CALCULATION INDICATING THE |
| | EXISTING AND NEW LOADS. |
| | 5. A PANEL SCHEDULE WITH A COMPLETE DIRECTORY OF |
| | CIRCUITRY AS IDENTIFIED ON THE FLOOR PLAN. A |
| | 6. A FIXTURE SCHEDULE INDICATING THE LIGHTING FIXTURES |
| | PROPOSED INDICATING LOCATIONS LAMP TYPE, LOAD AND |
| | VOLTAGE. |
| | 7. A SITE PLAN INDICATING THE LOCATION OF THE |
| | ELECTRICAL SERVICE. |
| | 8. CUT SHEETS OF ANY SPECIALZED EQUIPMENT PROPOSED SUCH |
| | AS STEAM GENERATORS, TRANSFER SWITCHES GENERATORS, HOME |
| | AUTOMATION EQUIPMENT, STRUCTURED CABLING CABINETS |
| | ETC... |
| | 9. REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO |
| | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND |
| | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS |
| | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON |
| | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH |
| | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 |
| | |
| | NOTE: ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI |
| | PROTECTED. NEC 210.12 |
| | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 |
| | PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOMS. |
| | NEC 210.11 (C) |
| | ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6 |
| | FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2 |
| | FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52 |
| | |
| | THESE ARE JUST TO NAME A FEW. PLEASE FAMILILIARIZE |
| | YOURSELF WITH THE 2008 EDITION OF THE NEC AND THE 2010 |
| | EDITION OF THE FBC AND THE WPB AMEMNDMENTS TO CHAPTER |
| | ONE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT |
| | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| | ITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND |
| | LEAVE THE PREVIOUSLY REVIEWED SHEETS. |
| | |