| 2014-07-02 13:48:51 | DATE: 7/2/2014 |
| | PROJECT: REVISION TO ATM REPLACEMENT. |
| | PERMIT#: 14070003 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION :PROVISO |
| | |
| | EACH OPERATOR, OR OTHER PERSON RESPONSIBLE FOR AN |
| | AUTOMATED TELLER MACHINE PURSUANT TO SECTIONS 655.960 |
| | THROUGH 655.965, SHALL PROVIDE LIGHTING DURING THE |
| | HOURS OF DARKNESS WITH RESPECT TO AN OPEN AND OPERATING |
| | AUTOMATED TELLER MACHINE AND ANY DEFINED PARKING AREA, |
| | ACCESS AREA AND THE EXTERIOR OF AN ENCLOSED AUTOMATED |
| | TELLER MACHINE INSTALLATION, AS FOLLOWS: |
| | |
| | 1) THERE SHALL BE A MINIMUM OF 10 FOOT CANDLE (108 LUX) |
| | POWER AT THE FACE OF THE AUTOMATED TELLER MACHINE AND |
| | EXTENDING IN AN UNOBSTRUCTED DIRECTION OUTWARD 5 FEET. |
| | |
| | 2) THERE SHALL BE A MINIMUM OF 2 FOOT CANDLE (21.5 LUX) |
| | POWER WITHIN 50 FEET (15.25 M) IN ALL UNOBSTRUCTED |
| | DIRECTIONS FROM THE FACE OF THE AUTOMATED TELLER |
| | MACHINE. IF THE AUTOMATED TELLER MACHINE IS LOCATED |
| | WITHIN 10 FEET (3 M) OF THE CORNER OF THE BUILDING AND |
| | THE AUTOMATED TELLER MACHINE IS GENERALLY ACCESSIBLE |
| | FROM THE ADJACENT SIDE, THERE SHALL BE A MINIMUM OF 2 |
| | FOOT CANDLE (21.5 LUX) POWER ALONG THE FIRST 40 |
| | UNOBSTRUCTED FEET (12 M) OF THE ADJACENT SIDE OF THE |
| | BUILDING. |
| | |
| | 3) THERE SHALL BE A MINIMUM OF 2 FOOT CANDLE (12.5 LUX) |
| | POWER IN THAT PORTION OF THE DEFINED PARKING AREA |
| | WITHIN 60 FEET (18 M) OF THE AUTOMATED TELLER MACHINE. |
| | |
| | 4) THE OPERATOR SHALL PROVIDE REFLECTIVE MIRRORS OR |
| | SURFACES AT EACH AUTOMATED TELLER MACHINE WHICH PROVIDE |
| | THE CUSTOMER WITH A REAR VIEW WHILE THE CUSTOMER IS |
| | ENGAGED IN USING THE AUTOMATED TELLER MACHINE |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |