2014-07-14 15:33:32****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. CALCULATIONS AND REPORTS TO BE IN A FORMAT
 ACCEPTABLE TO FBPE, SEE FAC61G15-23.
  
 2. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS 471.
  
 3. CALCULATIONS FOR EXISTING TOWER WAS DONE FOR
 EXPOSURE B. SEE FBC 1609 AND ASCE7-10, THIS PARCEL IS
 LOCATED IN EXPOSURE C. PLEASE REVISE.
  
 4. I WAS UNABLE TO LOCATE WIND DESIGN CRITERIA ON THE
 PLANS FOR THE PROPOSED CONSTRUCTION. SEE FBC 1603.1.4.
 PLEASE REVISE.
  
  