| Plan Review Notes For Permit 14061335 |
| Permit Number |
14061335 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-08-15 12:16:16 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR | | | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS | | | FS471. I BELIEVE THAT THIS MAY A REPEAT COMMENT FOR | | | THIS FIRM AND/OR ENGINEER. A SET HAS BEEN RETAINED. | | | | | | 2. THE STRUCTURAL ANALYSIS LETTER AND THE PLANS DO NOT | | | INCLUDE WIND DESIGN CRITERIA AS REQUIRED BY FBC | | | 1603.4.1. REVISE PLANS AND LETTER. | | | | | | 3. METHOD OF MOUNTING IS CONFUSING. SHEET E1 GROUNDING | | | PLAN REFERS TO RF DATA SHEET AND ALSO TO SHEET A11 | | | (WHICH DOES NOT EXIST IN THIS SET OF PLANS), NEITHER | | | WHICH SPECIFIES FASTENERS. THIS APPEARS TO BE DONE IN | | | THE LETTER. REVISE THE PLANS TO INCLUDE THE | | | SPECIFICATION OR REMOVE/REVISE THE ERRONEOUS | | | INFORMATION AND MAKE REFERENCE TO THE SPECIFIC LETTER | | | INCLUDING DATE. VERIFY THAT ALL DETAILS WHICH REFERENCE | | | OTHER SHEETS AND DETAILS ARE CORRECT. | | | | | | |
|