| 2015-07-09 13:40:50 | APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED |
| | PROVISIONALLY. FAILURE TO CORRECT THE LISTED |
| | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED |
| | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION |
| | FEE(S). |
| | |
| | NFPA 72.SECTION 29.8.3.4 SPECIFIC SMOKE DETECTOR |
| | LOCATION REQUIREMENTS: |
| | THE INSTALLATION OF SMOKE ALARMS AND SMOKE DETECTORS |
| | SHALL COMPLY WITH THE FOLLOWING REQUIREMENTS: |
| | (1) SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE |
| | LOCATED WHERE AMBIENT CONDITIONS, INCLUDING HUMIDITY |
| | AND TEMPERATURE, ARE OUTSIDE THE LIMITS SPECIFIED BY |
| | THE MANUFACTURER?S PUBLISHED INSTRUCTIONS. |
| | (2) SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE |
| | LOCATED WITHIN UNFINISHED ATTICS OR GARAGES OR IN OTHER |
| | SPACES WHERE TEMPERATURES CAN FALL BELOW 40?F (4?C) OR |
| | EXCEED 100?F (38?C). |
| | (3)*WHERE THE MOUNTING SURFACE COULD BECOME |
| | CONSIDERABLY WARMER OR COOLER THAN THE ROOM, SUCH AS A |
| | POORLY INSULATED CEILING BELOW AN UNFINISHED ATTIC OR |
| | AN EXTERIOR WALL, SMOKE ALARMS AND SMOKE DETECTORS |
| | SHALL BE MOUNTED ON AN INSIDE WALL. |
| | (4)*SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE |
| | INSTALLED WITHIN AN AREA OF EXCLUSION DETERMINED BY A |
| | 10 FT (3.0 M) RADIAL DISTANCE ALONG A HORIZONTAL FLOW |
| | PATH FROM A STATIONARY OR FIXED COOKING APPLIANCE, |
| | UNLESS LISTED FOR INSTALLATION IN CLOSE PROXIMITY TO |
| | COOKING APPLIANCES. SMOKE ALARMS AND SMOKE DETECTORS |
| | INSTALLED BETWEEN 10 FT (3.0 M) AND 20 FT (6.1 M) ALONG |
| | A HORIZONTAL FLOW PATH FROM A STATIONARY OR FIXED |
| | COOKING APPLIANCE SHALL BE EQUIPPED WITH AN |
| | ALARM-SILENCING MEANS OR USE PHOTOELECTRIC DETECTION. |
| | EXCEPTION: SMOKE ALARMS OR SMOKE DETECTORS THAT USE |
| | PHOTOELECTRIC DETECTION SHALL BE PERMITTED FOR |
| | INSTALLATION AT A RADIAL DISTANCE GREATER THAN 6 FT |
| | (1.8 M) FROM ANY STATIONARY OR FIXED COOKING APPLIANCE |
| | WHEN THE FOLLOWING CONDITIONS ARE MET: |
| | (A) THE KITCHEN OR COOKING AREA AND ADJACENT SPACES |
| | HAVE NO CLEAR INTERIOR PARTITIONS OR HEADERS AND |
| | (B) THE 10 FT (3.0 M) AREA OF EXCLUSION WOULD PROHIBIT |
| | THE PLACEMENT OF A SMOKE ALARM OR SMOKE DETECTOR |
| | REQUIRED BY OTHER SECTIONS OF THIS CODE. |
| | (5)*SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE |
| | INSTALLED WITHIN A 36 IN. (910 MM) HORIZONTAL PATH FROM |
| | A DOOR TO A BATHROOM CONTAINING A SHOWER OR TUB. |
| | (6) SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE |
| | INSTALLED WITHIN A 36 IN. (910 MM) HORIZONTAL PATH FROM |
| | THE SUPPLY REGISTERS OF A FORCED AIR HEATING OR COOLING |
| | SYSTEM AND SHALL BE INSTALLED OUTSIDE OF THE DIRECT |
| | AIRFLOW FROM THOSE REGISTERS. |
| | (7) SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE |
| | INSTALLED WITHIN A 36 IN. (910 MM) HORIZONTAL PATH FROM |
| | THE TIP OF THE BLADE OF A CEILING-SUSPENDED (PADDLE) |
| | FAN. |
| | (8) WHERE STAIRS LEAD TO OTHER OCCUPIED LEVELS, A SMOKE |
| | ALARM OR SMOKE DETECTOR SHALL BE LOCATED SO THAT SMOKE |
| | RISING IN THE STAIRWAY CANNOT BE PREVENTED FROM |
| | REACHING THE SMOKE ALARM OR SMOKE DETECTOR BY AN |
| | INTERVENING DOOR OR OBSTRUCTION. |
| | (9) FOR STAIRWAYS LEADING UP FROM A BASEMENT, SMOKE |
| | ALARMS OR SMOKE DETECTORS SHALL BE LOCATED ON THE |
| | BASEMENT CEILING NEAR THE ENTRY TO THE STAIRS. |
| | (10)*FOR TRAY-SHAPED CEILINGS (COFFERED CEILINGS), |
| | SMOKE ALARMS AND SMOKE DETECTORS SHALL BE INSTALLED ON |
| | THE HIGHEST PORTION OF THE CEILING OR ON THE SLOPED |
| | PORTION OF THE CEILING WITHIN 12 IN. (300 MM) |
| | VERTICALLY DOWN FROM THE HIGHEST POINT. |
| | (11) SMOKE ALARMS AND DETECTORS INSTALLED IN ROOMS WITH |
| | JOISTS OR BEAMS SHALL COMPLY WITH THE REQUIREMENTS OF |
| | 17.7.3.2.4. |
| | (12) HEAT ALARMS AND DETECTORS INSTALLED IN ROOMS WITH |
| | JOISTS OR BEAMS SHALL COMPLY WITH THE REQUIREMENTS OF |
| | 17.6.3. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |