| 2014-11-07 07:30:20 | RESIDENTIAL (R3) ALTERATION THIRD BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | ***NOTE: THESE COMMENTS APPLY TO FRONT BUILDING ONLY. |
| | REAR BUILDING COMMENTS ARE UNDER PERMIT #14061324. |
| | |
| | 1- SCOPE OF WORK IS NOT CLEAR. SCOPE OF WORK SPECIFIED |
| | ON SHEET A-1 DOESN'T REFLECT WHAT THE FLOOR PLANS SHOW |
| | AND WHAT THE PERMIT APPLICATION SPECIFIES. REVISE ALL L |
| | THE INFORMATION AS REQUIRED TO MATCH. SEC. 107.2.1 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | 2- REVISE VALUATION ON THE PERMIT APPLICATION TO MATCH |
| | ALL THE SCOPE OF WORK SPECIFIED IN THE REVISED |
| | INFORMATION REQUESTED ON ITEM #1 ABOVE. SEC. 109.3 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | 3- ENGINEER TO PROVIDE COMPLETE INFORMATION FOR THE NEW |
| | STAIRS AT THE BOTTOM RIGHT SIDE SHOWN ON THE ELECTRICAL |
| | PLAN. PROVIDE COMPLETE FRAMING DETAILS AND |
| | SPECIFICATIONS FOR NEW DOOR, INCLUDING SIZE. PROVIDE |
| | COMPLETE DETAILS AND SPECIFICATIONS FOR THE NEW STAIRS |
| | SHOWING COMPLIANCE WITH SEC. R311.3 OF 2010 FBC- |
| | RESIDENTIAL. INCLUDE THE REQUIRED LANDING AND RISER AND |
| | TREADS DIMENSIONS. |
| | |
| | 4- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) ANY NEW DOORS OR EXTERIOR DOORS TO BE REPLACED. |
| | B) ANY NEW WINDOWS OR WINDOWS TO BE REPLACED. |
| | C) ALL STRUCTURAL CONNECTORS SPECIFIED ON THE FRAMING |
| | DETAILS. PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE |
| | AND PAGE SHOWING THE SPECIFIED CONNECTOR. |
| | D) WINDOW MULLIONS, IF USED. |
| | E) ROOF SHINGLES IF THIS SCOPE OF WORK IS GOING TO BE |
| | INCLUDED. |
| | |
| | ***NOTE: THERE WERE SOME PRODUCT APPROVALS THAT WERE |
| | INLCUDED IN THIS PACKAGE. THEY HAD A DIFFERENT PERMIT |
| | NUMBER STAMPED ON THE FRONT COVER. THEY WERE ROUTED TO |
| | R12 SHELF TO RIDE ALONG WITH THAT PERMIT APPLICATION. |
| | |
| | 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS |
| | TO FBC. |
| | |
| | 6- IF REPLACING BEDROOM WINDOWS, THEN SPECIFY EXISTING |
| | WINDOW TYPE AND SIZE AND PROPOSED WINDOW TYPE AND SIZE |
| | TO VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENT OF |
| | SEC. 604 OF 2010 FBC-EXISTING BUILDING. |
| | |
| | 7- IF REPLACING DOOR AND WINDOWS, THEN CLEARLY IDENTIFY |
| | ON PLANS WHICH DOORS AND WINDOWS ARE GOING TO BE |
| | REPLACED. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| | |
| | ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected]. |