| 2014-11-13 10:10:40 | DATE:11/13/14 |
| | PROJECT: 3721 EASTVIEW |
| | PERMIT#: 14061324 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 3RD ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLANS AND NOTES ARE CONFLICTING. THE NOTES AND |
| | APPLICATION INDICATE ELECTRICAL SCOPE CONFORMING TO ALL |
| | CURRENT FBC AND NEC BUT THE EDITIONS OF THE CODES NOTED |
| | ARE NOT ACCURATE. THE PLANS WILL BE REVIEWED UNDER THE |
| | 2010 FBC AND THE 2008 NEC. THE SCOPE OF WORK ON THE |
| | APLICATION AND THE SCOPE OF WORK THAT APPEARS TO BE |
| | PROPOSED ON THE PLANS SUBMITTED ARE CONFLICTING. THE |
| | APPLICATION STATES THAT ONLY INTERIOIR FINISH ARE TO BE |
| | PERFORMED INVOLVING A/C, ELECTRIC, DRYWALL, TILE, AND |
| | PAINT. THE PLANS FOR THE REAR BUILDING INDICATE DEMO |
| | ONLY WITH A NEW GARAGE DOOR AND A GFI OUTLET. PLEASE |
| | ADDRESS ALL COMMENTS REGARDING THE PALNS SUBMITTED. |
| | |
| | 2) THE DEMOLITION PLAN INDICATES AN ELECTRICAL PANEL. |
| | THE NEW FLOOR PLAN HAS NO ELECTRICAL PANEL. PROVIDE |
| | INFORMATION TO CLARIFY WHERE AND HOW THE DEMOLISHED |
| | FEEDER IS TERMINATED AND WHERE AND HOW THE NEW BRANCH |
| | CIRCUIT COMES FROM TO FEED THE NEW GFI OUTLET. |
| | |
| | 3) AT LEAST ONE WALL SWITCH?CONTROLLED LIGHTING OUTLET |
| | SHALL BE INSTALLED IN HALLWAYS, STAIRWAYS, ATTACHED |
| | GARAGES, AND DETACHED GARAGES WITH ELECTRIC POWER. |
| | INDICATE THE REQUIRED LIGHTING OUTLET. NEC 210.70(2))A) |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM, SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO SUBMITTAL AND |
| | LEAVE THE PREVIOUSLY REVIEWED SHEETS. |
| | FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME. |
| | I CAN BE REACHED AT 561-805-6717 OR [email protected] |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |