| Plan Review Notes For Permit 14061324 |
| Permit Number |
14061324 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-07-06 14:51:56 | NOTE: THESE COMMENTS APPLY TO FRONT AND REAR BUILDINGS. | | | DRAWINGS A-1 TO A-5 SUBMITTED ARE FOR BOTH STRUCTURES: | | | | | | 1- CLARIFY WHERE IS THE GAF MINERAL GUARD RESIDENTIAL | | | ROLL ROOFING UNDERLAYMENT (NOA 13-1104.03) SUBMITTED | | | GOING TO BE INSTALLED? SEC. 107.2.1 CITY AMENDMENTS. | | | | | | 2- CLARIFY WHERE IS THE GAF CONVENTIONAL BUILT-UP ROOF | | | SYSTEM (NOA 13-1022.15) SUBMITTED GOING TO BE | | | INSTALLED?. SEC. 107.2.1 CITY AMENDMENTS. PLANS CALL | | | FOR EXISTING FLAT ROOF ON REAR BUILDING. NO RE-ROOF. IF | | | THIS BUILDING IS GOING TO BE RE-ROOFED, THEN NEED TO | | | IDENTIFY SPECIFIC ASSEMBLY TO BE INSTALLED AND PROVIDE | | | SIGNED AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY | | | GENERAL LIMITATION #7 ON LAST PAGE OF THE NOA. | | | | | | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | DCA RULE 9N-3 FOR: | | | A) ROOF SHINGLES. (REPEAT COMMENT. NO PRODUCT APPROVAL | | | SUBMITTED). | | | | | | |
|