| 2014-07-30 12:12:08 | DATE: 7/30/2014 |
| | PROJECT: 3721 EASTVIEW |
| | PERMIT#: 14061324 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLANS AND NOTES ARE CONFLICTING. THE NOTES AND |
| | APPLICATION INDICATE ELECTRICAL SCOPE CONFORMING TO ALL |
| | CURRENT FBC AND NEC BUT THE FLOORPLAN LAYOUT DO NOT |
| | CONFORM TO CODE. FBC 107.2.1. |
| | |
| | 2) A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL |
| | COUNTERTOP SPACE THAT IS 300 MM (12 IN.) OR WIDER. |
| | RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT |
| | ALONG THE WALL LINE IS MORE THAN 600 MM (24 IN.) |
| | MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT |
| | SPACE. NEC 210.52(C)(1) |
| | |
| | 3) A BUILDING OR OTHER STRUCTURE SERVED SHALL BE |
| | SUPPLIED BY ONLY ONE SERVICE . NEC 230.2. THE |
| | ELECTRICAL SERVICE IS INDICATED AS TWO SEPARTATE |
| | SERVICES ON ONE BUILDING. THE GROUNDING ELECTRODE |
| | SYSTEM IS INDICATED AS A SERVICE LATTERAL?? |
| | |
| | 4) AN INTER-SYSTEM BONDING TERMINATION FOR CONNECTING |
| | INTER-SYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED |
| | FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO |
| | ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE |
| | DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR |
| | STRUCTURES. NEC 250.94. |
| | |
| | 5) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. NEC 110.9 A FAULT CURRENT CALCULATION IS |
| | REQUIRED. |
| | |
| | 6) THE CALCULATED LOAD OF A FEEDER OR SERVICE SHALL NOT |
| | BE LESS THAN THE SUM OF THE LOADS ON THE BRANCH |
| | CIRCUITS SUPPLIED. NEC 220.40. PROVIDE A LOAD |
| | CALCULATION IN COMPLIANCE WITH NEC ARTICLE 220 ACTUAL |
| | LOAD CALCULATION REQUIRED BASED ON THE NEC ARTICLE 220. |
| | 220.1 SCOPE. THIS ARTICLE PROVIDES REQUIREMENTS FOR |
| | CALCULATING BRANCH-CIRCUIT, FEEDER, AND SERVICE LOADS. |
| | PART I PROVIDES FOR GENERAL REQUIREMENTS FOR |
| | CALCULATION METHODS. PART II PROVIDES CALCULATION |
| | METHODS FOR BRANCH-CIRCUIT LOADS. PARTS III AND IV |
| | PROVIDE CALCULATION METHODS FOR FEEDERS AND SERVICES. |
| | FABRICATING A TOTAL CONNECTED ELECTRICAL DEMAND BASED |
| | ON A PARTIAL PANEL SCHEDULE IS NOT AN APPROVED METHOD. |
| | |
| | 7) OUTLET BOXES OR OUTLET BOX SYSTEMS USED AS THE SOLE |
| | SUPPORT OF A CEILING-SUSPENDED (PADDLE) FAN SHALL BE |
| | LISTED, SHALL BE MARKED BY THEIR MANUFACTURER AS |
| | SUITABLE FOR THIS PURPOSE, AND SHALL NOT SUPPORT |
| | CEILING-SUSPENDED (PADDLE) FANS THAT WEIGH MORE THAN 32 |
| | KG (70 LB). FOR OUTLET BOXES OR OUTLET BOX SYSTEMS |
| | DESIGNED TO SUPPORT CEILING-SUSPENDED (PADDLE) FANS |
| | THAT WEIGH MORE THAN 16 KG (35 LB), THE REQUIRED |
| | MARKING SHALL INCLUDE THE MAXIMUM WEIGHT TO BE |
| | SUPPORTED. NEC 314(D) BOXES AT CEILING-SUSPENDED |
| | (PADDLE) FAN OUTLETS. NOTED ON PLANS. |
| | |
| | THE ABOVE LISTED NOTES ONLY NAME A FEW. IF THE INTENT |
| | OF THIS PERMIT APPLICATION AND ASSOCIATED CONSTRUCTION |
| | DOCUMENTS IS TO COMPLY WITH THE PROVISIONS OF ALL |
| | CURRENT CODES AND ORDINANCES PLEASE READ AND AND COMPLY |
| | WITH THE PROVISIONS OF THE 2008 EDITION OF THE NATIONAL |
| | ELECTRICAL CODE, AND THE 2010 EDITION OF THE FLORIDA |
| | BUILDING CODE AS WELL AS THE WEST PALM BEACH AMENDMENTS |
| | TO CHAPTER ONE OF THE FLORIDA BUILDING CODE. |
| | |
| | ADDITIONALLY, SEE BLDG. REVIEW COMMENTS BY JULIO GOMEZ |
| | WITH REGARDS TO ORIGNAL SCOPE OF WORK AND VALUATION ON |
| | ORIGINAL REVOKED PERMIT APPLICATION #10110533. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: HTTP://WPB.ORG/DEVELOPMENT |
| | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| | ITTAL_FORM_04132010.PDF |
| | |
| | PLEASE INSERT CORRECTED PAGES INTO SUBMITTAL PACKAGE |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |