| Plan Review Notes For Permit 14061270 |
| Permit Number |
14061270 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-08-06 16:49:03 | RESIDENTIAL (R3) ALTERATION, SECOND MECHANICAL REVIEW | | | CHECKLIST. | | | CODE: 2010 FBC. | | | | | | ****NOTE: THERE WAS NOT INFORMATION SUBMITTED TO | | | ADDRESS THE COMMENTS ON FIRST REVIEW. PLEASE ADDRESS | | | THE FOLLOWING COMMENTS FROM THE FIRST CHECKLIST: | | | | | | | | | | | | 1- PROVIDE COMPLETE INFORMATION FOR REVIEW: | | | A) EQUIPMENT SIZING CALCULATIONS WITH THE EQUIPMENT | | | MANUFACTURER AND MODEL AS REQUIRED BY SEC. 403.6 OF | | | 2010 FBC-ENERGY CONSERVATION. | | | | | | B) COMPLETE A/C PLAN WITH DUCT SYSTEMS AND EQUIPMENT | | | INFORMATION. EQUIPMENT TO MATCH EQUIPMENT SIZING | | | CALCULATIONS. SEC. 107.3.5.3(10) OF CITY AMENDMENTS TO | | | FBC | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT. | | | (561)805-6712 | | | [email protected] |
|