| 2014-08-06 15:02:36 | RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: 2010 FBC. |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS. SEC. 101.4.3 AND SEC. |
| | 103 OF 2010 FBC-ENERGY CONSERVATION. (REPEAT COMMENT. |
| | NOT ADDRESSED). |
| | (NOTE: THIS IS NOT A CONTRIBUTING HISTORIC HOUSE). |
| | |
| | 2- ENGINEER TO REVISE THE ROOF SHEATHING INFORMATION |
| | GIVEN ON SHEET A-1: |
| | A) NEED TO SPECIFY MIN. 8D RING SHANK NAILS WHICH ARE 2 |
| | 1/2" LONG NOT 1 1/4". SEE SEC. R803.2.3.1 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | B) ENGINEER TO CLARIFY WHY THE NAILING ZONES ARE PER |
| | RAS 117?. WHERE IS THIS INFORMATION TAKEN FROM? ROOF |
| | SHEATHING AND RAS 117 ARE TWO DIFFERENT THINGS. REVISE |
| | AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| | |
| | 3- ENGINEER TO REVISE EXTERIOR DOOR STRUCTURAL BUCK |
| | DETAIL ON SHEET A-2. NEED TO COMPLY WITH SEC. |
| | R612.10.2.1 OF 2010 FBC-RESIDENTIAL. NOTE: THE BUCKS |
| | NEED TO PROVIDE FULL SUPPORT TO THE DOOR FRAMING. 2" X |
| | 4" BUCK DOESN'T PROVIDE FULL SUPPORT TO THE DOOR FRAME. |
| | SEE DOOR PRODUCT APPROVAL FOR DOOR FRAME SIZE AND |
| | REVISE AS REQUIRED. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) USP HC10 AND USP RT18T STRUCTURAL TRUSS CONNECTORS |
| | SPECIFIED ON DETAILS ON SHEET A-1. ***NOTE: PROVIDE |
| | ONLY THE PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING |
| | THE SPECIFIED CONNECTOR. (REPEAT COMMENT NOT |
| | ADDRESSED). |
| | |
| | B) FIXED WINDOWS. NEED TO PROVIDE COMPLETE DRAWINGS. |
| | DRAWINGS SUBMITTED WITH NOA 10-1015.02 ARE INCOMPLETE |
| | AND CUT. NEED COMPLETE DRAWINGS. (REPEAT COMMENT. NOT |
| | ADDRESSED). |
| | |
| | C) NEW COMMENT: SINGLE HUNG NOA 11-0404.09 AND EXTERIOR |
| | DOOR NOA 09-0608.16 SUBMITTED NOW ARE FOR NON-IMPACT |
| | WINDOWS AND DOORS. THEREFORE, NEED TO PROVIDE PRODUCT |
| | APPROVAL (2 COPIES) FOR HURRICANE SHUTTERS AS REQUIRED |
| | BY SEC. 606.4 OF 2010 FBC-EXISTING BUILDING. |
| | |
| | 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 |
| | OF CITY AMENDMENTS TO FBC. |
| | |
| | 6- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE |
| | INSTALLATION OF THE HURRICANE SHUTTERS. THERE IS A CITY |
| | HURRICANE SHUTTERS INSTALLATION CHART THAT YOU CAN USE |
| | OR YOU CAN PROVIDE A DIFFERENT FORMAT THAT PROVIDES ALL |
| | THE INFORMATION REQUESTED IN THE CITY SAMPLE. SEC. |
| | 107.2.1 CITY AMENDMENTS TO FBC. |
| | |
| | |
| | ***NOTES: |
| | *PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH COMMENT |
| | TO EXPEDITE THE REVIEW PROCESS. |
| | *PLEASE REPLACE ANY REVISE SHEET. |
| | |