| Plan Review Notes For Permit 14061270 |
| Permit Number |
14061270 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-07-22 15:14:06 | RESIDENTIAL (R3) ALTERATION, PLUMBING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- KITCHEN PLUMBING RISER DIAGRAM: THE CLOTHES WASHING | | | MACHINE VENTING AND WASTE IS INCORRECT. SEE SEC. P2718 | | | OF 2010 FBC-RESIDENTIAL AND SEC. P3005.1.1. APPLIANCES | | | WITH PUMPING ACTION DISCHARGE CAN NOT BE CONNECTED TO | | | THE KITCHEN BRANCH AS SHOWN ON PLUMBING RISER DIAGRAM. | | | REVISE AS REQUIRED. | | | | | | ***NOTE: PLUMBING RISER DIAGRAM MAY BE DRAWN BY THE | | | LICENSED CONTRACTOR DOING THE WORK. IF DOING SO, | | | CONTRACTOR TO PROVIDE NAME AND SIGNATURE ON PLUMBING | | | RISER DIAGRAM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|