| Date |
Text |
| 2014-07-22 14:40:59 | RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- PROVIDE COMPLETE INFORMATION FOR REVIEW: | | | A) EQUIPMENT SIZING CALCULATIONS WITH THE EQUIPMENT | | | MANUFACTURER AND MODEL AS REQUIRED BY SEC. 403.6 OF | | | 2010 FBC-ENERGY CONSERVATION. | | | | | | B) COMPLETE A/C PLAN WITH DUCT SYSTEMS AND EQUIPMENT | | | INFORMATION. EQUIPMENT TO MATCH EQUIPMENT SIZING | | | CALCULATIONS. SEC. 107.3.5.3(10) OF CITY AMENDMENTS TO | | | FBC | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT. | | | (561)805-6712 | | | [email protected] |
|