| 2014-07-21 11:32:22 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS. SEC. 101.4.3 OF 2010 |
| | FBC-ENERGY CONSERVATION. |
| | (NOTE: NOT A CONTRIBUTING HISTORIC HOUSE). |
| | |
| | 2- ENGINEER TO PROVIDE COMPLETE DETAIL AND |
| | SPECIFICATIONS FOR GABLE END WALL SHOWING COMPLIANCE |
| | WITH SEC. R609.4 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 3- PROVIDE COMPLETE SPECIFICATIONS FOR THE NEW ROOF |
| | SHEATHING. SPECIFY MATERIAL AND FASTENER TYPE AND |
| | SPACING. SEE SEC. R803.2.3.1 FOR MINIMUM TYPE OF NAIL |
| | AND SPACING TO BE USED, INCLUDING ROOF ZONE #3. |
| | |
| | 4- PROVIDE COMPLETE SPECIFICATIONS FOR THE ROOF |
| | VENTILATION AS REQUIRED BY SEC. R806. |
| | |
| | 5- A) REVISE ALL WINDOW STRUCTURAL BUCK DETAILS ON |
| | SHEET A-2. PROVIDE COMPLETE SPECIFICATIONS FOR SIZE AND |
| | FASTENING OF WINDOW BUCKS. REVISE DETAILS TO COMPLY |
| | WITH SEC. R612.10.2.1 OF 2010 FBC-RESIDENTIAL. NOTE: |
| | THE BUCKS NEED TO PROVIDE FULL SUPPORT TO THE WINDOW |
| | FRAMING. REVISE DETAILS AS REQUIRED. |
| | |
| | B) PROVIDE COMPLETE STRUCTURAL BUCK DETAIL FOR DOORS. |
| | SEC. R612.10.2.1. COORDINATE WITH COMMENT 5(A) ABOVE. |
| | |
| | 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) SINGLE HUNG WINDOWS TO BE INSTALLED. |
| | |
| | B) WINDOW MULLIONS. AND CLEARLY IDENTIFY MULLION SIZE |
| | AND FASTENING TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES. |
| | |
| | C) USP HC10 AND USP RT18T STRUCTURAL TRUSS CONNECTORS |
| | SPECIFIED ON DETAILS. ***NOTE: PROVIDE ONLY THE PRODUCT |
| | APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED |
| | CONNECTOR |
| | |
| | D) FIXED WINDOWS. NEED TO PROVIDE COMPLETE DRAWINGS. |
| | DRAWINGS SUBMITTED WITH NOA 10-1015.02 ARE CUT. NEED |
| | COMPLETE DRAWINGS. |
| | |
| | 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL THE PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC. |
| | |
| | 8- BEDROOM WINDOWS TO BE REPLACED: SPECIFY EXISTING |
| | TYPE AND SIZE OF EXITING WINDOWS TO BE REPLACED TO |
| | VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. |
| | 604.1 OF 2010 FBC-EXISTING BUILDING. |
| | |
| | 9- REVISE WINDOW SCHEDULE. THERE ARE NO ALUMINUM CLAD |
| | WOOD WINDOWS. SEE PRODUCT APPROVALS SUBMITTED AND |
| | REVISE AS REQUIRED. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | ***NOTE: PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS... |
| | |