| 2014-07-09 15:59:53 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2010 |
| | |
| | 1. NA - THIS STRUCTURE IS NOW POST FIRM (ORIGINAL |
| | ELEVATION CERTIFICATE RECEIVED VIA MAIL 9/2) |
| | |
| | 2. DESIGN PRESSURES ARE TOO LOW. SEE FBC 1609, |
| | ASCE7-10. ZONE 4, +28/-30.7 REQUIRED FOR 50-100SF, |
| | +28/-35.3 REQUIRED FOR ZONE 5. PLEASE REVISE WIND LOAD |
| | CHART ACCORDINGLY OR PROVIDE ENGINEERING WITH |
| | CALCULATIONS FOR PROPOSED DESIGN PRESSURES. |
| | |
| | 3. BLOCKING OF EXITS (COMMERCIAL BUILDINGS) WITH |
| | SHUTTERS IS NOT PERMITTED IN THE BUILDING CODE AND IS |
| | CONSIDERED ON A CASE BY CASE BASIS. SEE THE FOLLOWING |
| | CODE SECTIONS: |
| | |
| | FBC 1003.6, MEANS OF EGRESS CONTINUITY. THE PATH OF |
| | EGRESS TRAVEL ALONG A MEANS OF EGRESS SHALL NOT BE |
| | INTERRUPTED BY ANY BUILDING ELEMENT OTHER THAN A MEANS |
| | OF EGRESS COMPONENT AS SPECIFIED IN THIS CHAPTER. |
| | OBSTRUCTIONS SHALL NOT BE PLACED IN THE REQUIRED WIDTH |
| | OF A MEANS OF EGRESS EXCEPT PROJECTIONS PERMITTED BY |
| | THIS CHAPTER. |
| | |
| | 1008.1.4.5 SECURITY GRILLS. IN GROUPS B, F, M, R AND S, |
| | HORIZONTAL SLIDING OR VERTICAL SECURITY GRILLES ARE |
| | PERMITTED AT THE MAIN EXIT AND SHALL BE OPENABLE FROM |
| | THE INSIDE WITHOUT THE USE OF A KEY OR SPECIAL |
| | KNOWLEDGE OR EFFORT DURING PERIODS THAT THE SPACE IS |
| | OCCUPIED. THE GRILLES SHALL REMAIN SECURED IN THE |
| | FULL-OPEN POSITION DURING THE PERIOD OF OCCUPANCY BY |
| | THE GENERAL PUBLIC. WHERE TWO OR MORE MEANS OF EGRESS |
| | ARE REQUIRED, NOT MORE THAN ONE-HALF OF THE EXITS OR |
| | EXIT ACCESS DOORWAYS SHALL BE EQUIPPED WITH HORIZONTAL |
| | SLIDING OR VERTICAL SECURITY GRILLES. |
| | |
| | PROVIDE A LIFE SAFETY PLAN SO RISK CAN BE EVALUATED. |
| | |
| | 3. SEE PAGE 5 OF 8 ON THE PRODUCT APPROVAL 812. A NOTE |
| | HAS BEEN ADDED THAT THE SCREENS WILL SHARE ANCHORS AS |
| | NECESSARY. ANY MOFIDICATION TO THE PRODUCT APPROVALS |
| | ARE TO BE DONE BY AN ENGINEER. REMOVE ANY NOTES WHICH |
| | MODIFY INSTALLATION INSTRUCTIONS. |
| | |
| | |
| | |