Plan Review Notes
Plan Review Notes For Permit 14061244
Permit Number 14061244
Review Stop B
Sequence Number 1
Notes
Date Text
2014-07-09 06:30:29BUILDING PLAN REVIEW
 PERMIT: 14061244
 ADD: 4440 BEACON CIRCLE
 CONT: STRUCTURE TECH
 TEL: (305)233-1100
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JULY 09/2014
 ACTION: DENIED
  
 1) ARCHITECTURAL & STRUCTURAL SHEETS DESIGNED BY GE
 HEALTHCARE ARE NOT SIGNED NOR SEALED. 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION, 107.1 THE CONSTRUCTION DOCUMENTS
 SHALL BE PREPARED BY A REGISTERED DESIGN WHERE REQUIRED
 BY CHAPTER 471, FLORIDA STATUTES& 61G15 FLORIDA
 ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES&
 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE SPECIAL
 CONDITIONS EXIST, THE BUILDING OFFICIAL IS AUTHORIZED
 TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS TO BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL.
  
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 2) THE ARCHITECTURAL & STRUCTURAL SHEETS DESIGNED BY GE
 HEALTHCARE HAVE NOT BEEN REVIEWED BY THE DESIGNER OF
 RECORD AND THEIR SHOP DRAWING STAMP OF APPROVAL
 AFFIXED. FL 61G1-23.015 (2) THE ARCHITECT IS
 RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL PROJECT
 DATA, REPORTS, SHOP DRAWINGS ETC...
  
 3) THE GE HEALTHCARE ARCHITECTURAL SHEET NOTE 67
 INDICATES A 9'-0" X 9'-0" SECTION OF EXTERIOR WALL IS
 TO BE REMOVED AND REBUILT AFTER THE OLD EQUIPMENT
 REMOVED AND THE NEW EQUIPMENT IS INSTALLED.AGAIN THERE
 IS NO DESIGN PROFESSIONAL TAKING RESPONSIBILITY FOR THE
 DESIGN.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
  
 4) SHEET A3 MRI FOUNDATION AND FLOOR DETAIL, THE SIZE
 OF THE THICKNESS (HEIGHT) OF THE FOUNDATION IS NOT
 PROVIDED NOR IS THE THICKNESS OF THE FLOOR SLAB. THE
 PSI OR MIX TYPE OF CONCRETE FOR THE FOUNDATION AND SLAB
 ARE NOT PROVIDED
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  