| 2014-07-17 14:07:24 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | 1- REVISE ENERGY CALCULATIONS FORM 402-2010 SUBMITTED: | | | A) NEED TO INSTALL ALL THE VALUES THAT ARE LISTED ON | | | TABLE 402A (SECOND PAGE) OF FORM SUBMITTED. REVISE PAGE | | | ONE AND PAGE TWO AS REQUIRED. | | | | | | ***NOTE: | | | PERFORMANCE FORM 405 MAY ALSO BE USED INSTEAD OF THE | | | PRESCRIPTIVE FORM 402. ( ALL THE REQUIREMENTS OF | | | PRESCRIPTIVE FORM 402 MUST BE INSTALLED AND NEED TO | | | PROVIDE MORE INFORMATION SHOWING HOW ACHIEVING THOSE | | | VALUES LISTED IN TABLE 402A) | | | | | | 2- PROVIDE PRODUCT APPROVAL FOR: | | | A) NON-IMPACT SINGLE HUNG WINDOWS. | | | | | | B) WINDOW MULLIONS. | | | | | | 3- ABOVE PRODUCT APPROVALS NEED TO BE REVIEWED AND | | | APPROVED IN WRITING BY THE ENGINEER OF RECORD. | | | | | | 4- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE STORM | | | SHUTTERS. SEE CITY SAMPLE. |
|