Plan Review Notes
Plan Review Notes For Permit 14061218
Permit Number 14061218
Review Stop P
Sequence Number 1
Notes
Date Text
2014-07-08 12:27:03PLUMBING PLAN REVIEW
 PERMIT: 14061218
 ADD: 2921 N AUSTRALIAN AVE
 CONT: TBD
 TEL: (561)827-4920
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES.JULY 08/2014
 ACTION: DENIED
 CHANGE OF OCCUPANCY TO EVENT HALL
  
 1)MISSING INFORMATION REQUIRED FOR A COMMERCIAL PLAN
 REVIEW.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, 107.3.5 MINIMUM PLAN REVIEW CRITERIA
 FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.3 PLUMBING
 1. PROVIDE THE OCCUPANT LOADS FROM THE BUILDING
 OCCUPANT LOAD AND SEE WHAT THE MINIMUM FIXTURE COUNT
 WILL BE. MINIMUM PLUMBING FACILITIES. 403.1.3.2
 OCCUPANCY CONTENT CALCULATION.
 THE OCCUPANCY CONTENT OF A BUILDING, WHICH DETERMINES
 THE NUMBER OF WATER CLOSETS REQUIRED FOR MEN, SHALL BE
 CALCULATED USING THE SQUARE FOOTAGE PER PERSON
 REQUIREMENTS ESTABLISHED BY THE FLORIDA BUILDING CODE,
 BUILDING.
  
 2) 2010 FBC-PLUMBING TABLE 403.1 MINIMUM NUMBER OF
 REQUIRED PLUMBING FIXTURES 403.3 REQUIRED PUBLIC TOILET
 FACILITIES.
 CUSTOMERS, PATRONS AND VISITORS SHALL BE PROVIDED WITH
 PUBLIC TOILET FACILITIES IN STRUCTURES AND TENANT
 SPACES INTENDED FOR PUBLIC UTILIZATION. THE NUMBER OF
 PLUMBING FIXTURES LOCATED WITHIN THE REQUIRED TOILET
 FACILITIES SHALL BE PROVIDED IN ACCORDANCE WITH SECTION
 403 FOR ALL USERS. EMPLOYEES SHALL BE PROVIDED WITH
 TOILET FACILITIES IN ALL OCCUPANCIES. EMPLOYEE TOILET
 FACILITIES SHALL BE EITHER SEPARATE OR COMBINED
 EMPLOYEE AND PUBLIC TOILET FACILITIES.
  
 3) 2010 FL ACCESSIBILITY CODE 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]