| 2014-09-04 12:00:56 | DATE: 9/4/2014 |
| | PROJECT: CHAPEL BY THE LAKE COU TO EVENT CENTER |
| | PERMIT#: 14061218 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. WPB AMENDMENTS TO THE FBC |
| | 107.2.1. THERE IS NO ELECTRICAL INFORMATION ON THE |
| | SUBMITTAL TO REVIEW. SEE BELOW FOR THE MINIMUM PLAN |
| | REVIEW CRITERIA FOR ELECTRICAL WORK: |
| | A.) 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, SECTION 107.3.5 MINIMUM PLAN REVIEW |
| | CRITERIA FOR BUILDINGS.107.3.5.1.2 ELECTRICAL |
| | 1. ELECTRICAL: WIRING, SERVICES, FEEDERS AND BRANCH |
| | CIRCUITS, OVERCURRENT PROTECTION, GROUNDING, WIRING |
| | METHODS AND MATERIALS, GFCI'S |
| | 2. EQUIPMENT |
| | 3. SPECIAL OCCUPANCIES |
| | 4. EMERGENCY SYSTEMS |
| | 5. COMMUNICATION SYSTEMS |
| | 6. LOW VOLTAGE |
| | 7. LOAD CALCULATIONS |
| | 8. DESIGN FLOOD ELEVATION |
| | |
| | 2) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS |
| | TO FBC 107.2.1. |
| | THE PLANS SUBMITTED SHALL BE SIGNED BY THE DESIGN |
| | PROFESSIONAL RESPONSIBLE FOR THE DESIGN. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |