| Date |
Text |
| 2016-03-17 15:45:12 | 3RD ELECTRICAL REVIEW NOTES FOR PERMIT 14061217 |
| | REVIEWED FOR COMPLIANCE WITH: 2010 FBC & NEC 2008 |
| | |
| | BELOW ARE THE COMMENTS RESPONSES TO THE SECOND REVIEW. |
| | TO SIMPLIFY MATTERS I HAVE USED THE SAME FORMAT OF THE |
| | PREVIOUS REVIEW AND DELETED ALL THE SATISFACTORILY |
| | ADDRESSED AND ONLY LEFT THE ONES REQUIRING FURTHER |
| | ATTENTION. FURTHERMORE, ALL SHOW WINDOW AND SIGN OUTLET |
| | REQUIREMENTS HAVE BEEN DEFFERED TO THE TENANT |
| | BUILD-OUT. |
| | |
| | PAGE 201 |
| | 2. PER THE SAME CODE, AUTOMATIC LIGHTING CONTROLS ARE |
| | REQUIRED IN THE ENTRY HALLWAYS. |
| | (A) PER FBC-E 505.2.1 EVERY AREA ENCLOSED BY WALLS OR |
| | FLOOR TO CEILING PARTITIONS SHALL HAVE AT LEAST ONE |
| | CONTROL DEVICE TO CONTROL THE LIGHTING WITHIN THE |
| | SPACE. THIS MEANS SEPARATE LIGHT SWITCHES ARE REQUIRED |
| | IN THE TOILET AREA, MAIN BATH AREA AND CLOSET. |
| | FURTHERMORE, FBC-M SECTION 401.3 REQUIRES THAT |
| | VENTILATION BE PROVIDED WHENEVER THE SPACE IS OCCUPIED |
| | THEREFORE THE EXHAUST FANS SHALL BE TIED TO THE |
| | LIGHTING. |
| | 3. THERE ARE NO ELECTRICAL OUTLETS SHOWN ON THE |
| | DRAWINGS FOR THE GUEST ROOMS. GUEST ROOM OUTLETS SHALL |
| | BE INSTALLED AND SPACED ACCORDING TO NEC 210.52 (A) & |
| | (D). |
| | (A) RECEPTACLES AS INDICATED ON PLANS DO NOT COMPLY |
| | WITH THE MINIMUM CODE REQUIREMENTS OF NEC 210.52(A)(1). |
| | 4. THOUGH NEC REQUIRES TAMPER?RESISTANT RECEPTACLES FOR |
| | DWELLING UNITS NOT SPECIFICALLY GUEST ROOMS, THE |
| | INSTALLATION OF TAMPER?RESISTANT DEVICES IS A |
| | SUGGESTION. |
| | (A) RESPONSE COMPLIANT W/NEC 2008 THOUGH REQUIRED IN |
| | CURRENT CODE. |
| | |
| | PAGE 301 |
| | 1. THERE IS NO LIGHTING REFLECTED FOR THE VARIOUS |
| | ROOMS. AS PER THE VARIOUS CODES ALL THESE ROOMS REQUIRE |
| | ILLUMINATION AS WELL AS EMERGENCY LIGHTING. AUTOMATIC |
| | CONTROLS AS PER FBC?E SHALL BE INSTALLED AS REQUIRED. |
| | (A) RESPONSE ACCEPTED HERE SEE NOTE ABOVE. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |