| Date |
Text |
| 2015-05-22 14:54:54 | 1. PLEASE ADDRESS OUT PREVIOUS COMMENTS FROM THE 2014 |
| | REVIEW. |
| | |
| | 2. GREASE TRAPS ARE PROPOSED WITHIN THE BUILDING, IN |
| | THE SAME SPACE INTENDED FOR THE TRASH DUMPSTERS / |
| | COMPACTORS. PLEASE VERIFY THAT THE PROPOSED SIZE AND |
| | QUANTITY OF TRASH BINS IS APPROPRIATE FOR THE WASTE |
| | YARDAGE ANTICIPATED TO BE GENERATED BY THE COMPLEX. |
| | DEMONSTRATE THAT THE NEEDED DUMPSTER(S) WILL FIT WITHIN |
| | THE PROPOSED BUILDING. CONSIDER USING A COMPACTOR TO |
| | REDUCE THE YARDAGE OF WASTE THAT WILL NEED TO BE |
| | COLLECTED. (SHEET P101) |
| | |
| | 3. PLEASE DEMONSTRATE THAT THE PROPOSAL TO ROLL THE |
| | TRASH BINS INTO THE ALLEY WILL NOT IMPEDE TRAFFIC FLOW |
| | WHILE THE BINS ARE IN THE ALLEY OR COMPLETELY BLOCK |
| | TRAFFIC WHEN THE SOLID WASTE TRUCKS ARE COLLECTING THE |
| | GARBAGE. |
| | |
| | 4. PLEASE CONNECT THE FIRE RISER DRAIN TO THE SANITARY |
| | SYSTEM RATHER THAN THE STORMWATER SYSTEM. PER NFPA |
| | STANDARDS: THE DRAIN SHOULD BE PIPED TO A SUMP, WHICH |
| | IN TURN SHOULD DISCHARGE BY GRAVITY OR BE PUMPED TO A |
| | WASTE WATER DRAIN OR SEWER. (SHEET FS 201) |
| | |
| | 5. PLEASE DISCUSS THE PROPOSED SANITARY CONNECTION |
| | LOCATION WITH PUBLIC WORKS STAFF. THE CITY IS IN THE |
| | PROCESS OF ABANDONING UTILITIES WITHIN ALLEYS DUE TO |
| | THEIR AGE AND DIFFICULTY PERFORMING MAINTENANCE AND |
| | REPAIR ACTIVITIES. THE SANITARY CONNECTION MAY NEED TO |
| | BE RELOCATED TO THE MAIN LINE ALONG DIXIE. |
| | |
| | |
| | KELLY CRANFORD, P.E. |
| | LAND DEVELOPMENT ENGINEER |
| | PUBLIC WORKS DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | 561-494-1098 (OFFICE) |
| | |
| | |
| | |
| | |