| 2015-09-09 16:37:15 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE SECOND REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| | PAGE E101 |
| | 1. NEC 600.5 REQUIRES A DEDICATED SIGN OUTLET AT EACH |
| | ENTRANCE OF A COMMERCIAL BLDG. IN THIS CASE, THERE ARE |
| | THREE MARKED ON THE PLANS. |
| | 2. NEC 210.62 STATES THAT AT LEAST 1 OUTLET BE |
| | INSTALLED WITHIN 18? OF THE TOP OF A SHOW WINDOW FOR |
| | EACH 12? OF WINDOW OR PORTION THEREOF. |
| | 3. ADDITIONAL LIGHTING SHALL BE INSTALLED IN STAIR 3. |
| | SWITCHING TO CODE. |
| | PAGE 104 |
| | 1. SAME AS NUMBER 1 ABOVE. THE S.E. DOOR MAY NOT |
| | REQUIRE THIS IF IT IS AN INTERIOR DOOR. |
| | 2. THE SAME APPLIES TO ?FLEX SPACE? 1, 2 & 3. |
| | PAGE 201 |
| | 1. PER FBC-ENERGY SECTION 505.2.1.3(3) HOTEL ROOMS |
| | SHALL HAVE A MASTER SWITCH AT THE ENTRY DOOR TO ALL |
| | LIGHTING AND SWITCHED OUTLETS IN THE ROOM. |
| | 2. PER THE SAME CODE, AUTOMATIC LIGHTING CONTROLS ARE |
| | REQUIRED IN THE ENTRY HALLWAYS. |
| | 3. THERE ARE NO ELECTRICAL OUTLETS SHOWN ON THE |
| | DRAWINGS FOR THE GUEST ROOMS. GUEST ROOM OUTLETS SHALL |
| | BE INSTALLED AND SPACED ACCORDING TO NEC 210.52 (A) & |
| | (D). |
| | 4. THOUGH NEC REQUIRES TAMPER-RESISTANT RECEPTACLES FOR |
| | DWELLING UNITS NOT SPECIFICALLY GUEST ROOMS, THE |
| | INSTALLATION OF TAMPER-RESISTANT DEVICES IS A |
| | SUGGESTION. |
| | 5. FBC-907.2.11.1 REQUIRES THAT SINGLE STATION SMOKE |
| | DETECTORS BE INSTALLED IN EVERY GUEST ROOM. |
| | PAGE 301 |
| | 1. THERE IS NO LIGHTING REFLECTED FOR THE VARIOUS |
| | ROOMS. AS PER THE VARIOUS CODES ALL THESE ROOMS REQUIRE |
| | ILLUMINATION AS WELL AS EMERGENCY LIGHTING. AUTOMATIC |
| | CONTROLS AS PER FBC-E SHALL BE INSTALLED AS REQUIRED. |
| | 2. ACCORDING TO THE RISER DIAGRAM, PANEL IL IS TO BE |
| | INSIDE THE MAIN ELECTRICAL ROOM, BUT IT IS NOT |
| | INDICATED ON DETAIL 4 OF THIS PAGE. |
| | 3. THE RISER REFLECT PANEL IL AS A SINGLE UNIT, YET THE |
| | PANEL SCHEDULE SHEET SHOWS TWO SEPARATE PANELS. |
| | 4. THE RISER DIAGRAM DOES NOT MATCH THE PANEL SCHEDULE |
| | AS SHOWN ON THE DRAWINGS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU |
| | |