| 2015-05-22 16:10:56 | BUILDING PLAN REVIEW |
| | PERMIT: 14061217 |
| | ADD: 335 CLEMATIS ST |
| | CONT: TBD |
| | TEL: (561)856-6655/ NEYITA |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2ND REVIEW |
| | DATE: FRI. MAY 22 2015 |
| | ACTION: DENIED |
| | |
| | 1) PROVISO: THE SURVEY INDICATES THE PROPOSED BUILDING |
| | WILL PROVIDE A REPLAT BEFORE PERMIT ISSUANCE. |
| | |
| | 2) THRESHOLD BUILDINGS. |
| | |
| | 2A) COMPLIED, 109.3.6.1 SUBMITTED A WRITTEN THRESHOLD |
| | PLAN. |
| | |
| | 2B) COMPLIED. |
| | |
| | 2C) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT |
| | 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS |
| | REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE |
| | MINIMUM INSPECTIONS REQUIRED BY THIS CODE.THE THRESHOLD |
| | AGREEMENT FORMS MUST BE SIGNED BY ALL INTERESTED |
| | PARTIES AND RETURNED TO THE BUILDING DEPARTMENT BEFORE |
| | PERMIT ISSUANCE. . CONTACT KEN CONRAD MANAGER OF THE |
| | SPECIAL INSPECTOR PROGRAM AT (561)805-6666 OR E-MAIL: |
| | [email protected] FOR FURTHER INFORMATION. |
| | |
| | 2D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE |
| | PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS |
| | PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL |
| | CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL |
| | OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE |
| | RESUME' IS REVIEWED, AN INTERVIEW WILL BE REQUIED. |
| | |
| | 2E) 2ND REQUEST. THE CONTRACTOR OF RECORD WILL PRODUCE |
| | A JOB SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN |
| | CONRAD: [email protected] |
| | |
| | 2F) NOTICE ONLY, NO ACTION REQUIRED BY ARCHITECT. |
| | PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| | IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. |
| | |
| | 2G) NOTICE ONLY, NO ACTION REQUIRED BY ARCHITECT. |
| | 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR |
| | THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER HAS |
| | REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, |
| | APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND |
| | CEILINGS. |
| | |
| | 3-4) COMPLIED. |
| | |
| | 5) 2ND REQUEST. NOTE, 3 ADDITIONAL WRITTENTHRESHOLD |
| | INSPECTION PLANS WERE SUBMITTED. SHEET S11.1 FOUNDATION |
| | NOTE # 1 ARDAMAN & ASSOCIATES HAS COMPLETED A SOILS |
| | REPORT DATED MAY 14/ 2014. PLEASE SUPPLY THE BUILDING |
| | DEPARTMENT WITH (3) ORIGINAL SIGNED & SEALED REPORTS. |
| | 1803.3 BASIS OF INVESTIGATION. SOIL CLASSIFICATION |
| | SHALL BE BASED ON OBSERVATION AND ANY NECESSARY TESTS |
| | OF THE MATERIALS DISCLOSED BY BORINGS, TEST PITS OR |
| | OTHER SUBSURFACE EXPLORATION MADE IN APPROPRIATE |
| | LOCATIONS. ADDITIONAL STUDIES SHALL BE MADE AS |
| | NECESSARY TO EVALUATE SLOPE STABILITY, SOIL STRENGTH, |
| | POSITION AND ADEQUACY OF LOAD-BEARING SOILS, THE EFFECT |
| | OF MOISTURE VARIATION ON SOIL-BEARING CAPACITY, |
| | COMPRESSIBILITY, LIQUEFACTION AND EXPANSIVENESS. |
| | |
| | 6) COMPLIED. |
| | |
| | 7) SHEET A1.00 LIFE SAFETY SHEET: |
| | 7A-D) COMPLIED. |
| | |
| | |
| | 7E) PLEASE PROVIDE COMPLIANCE A MEETING WITH OTHER |
| | DESIGNERS MAY BE REQUIRED. |
| | EMERGENCY POWER NOTES DON'T SHOW COMPLIANCE WITH 2010 |
| | FBC-B [F] 403.4.8.1 EMERGENCY POWER LOADS. |
| | THE FOLLOWING ARE CLASSIFIED AS EMERGENCY POWER LOADS: |
| | 403.4.8.1: |
| | (3.) EMERGENCY VOICE/ALARM COMMUNICATIONS SYSTEMS; |
| | |
| | (4.) AUTOMATIC FIRE DETECTION SYSTEMS; |
| | |
| | (5.) FIRE ALARM SYSTEMS; AND |
| | |
| | (6.) ELECTRICALLY POWERED FIRE PUMPS. |
| | |
| | 7F) (1) COMPLIED. (1) FIRE PUMP) THE LIFE SAFETY SHEET |
| | LEVEL 1 DOES NOT INDICATE COMPLIANCE WITH 403.3.2 WATER |
| | SUPPLY TO REQUIRED FIRE PUMPS. |
| | |
| | 7F)(2) @ND REQUEST. CIVIL SHEET 09 DOES NOT SHOW WATER |
| | FROM 2 DIFFERENT MAINS. 2010 FBC-B 403.3.2 2 REQUIRED |
| | MAINS. REQUIRED FIRE PUMPS SHALL BE SUPPLIED BY |
| | CONNECTIONS TO A MINIMUM OF TWO WATER MAINS LOCATED IN |
| | DIFFERENT STREETS. SEPARATE SUPPLY PIPING SHALL BE |
| | PROVIDED BETWEEN EACH CONNECTION TO THE WATER MAIN AND |
| | THE PUMPS. EACH CONNECTION AND THE SUPPLY PIPING |
| | BETWEEN THE CONNECTION AND THE PUMPS SHALL BE SIZED TO |
| | SUPPLY THE FLOW AND PRESSURE REQUIRED FOR THE PUMPS TO |
| | OPERATE. THE EXCEPTION WOULD STILL REQUIRE THE MAINS TO |
| | BE VALVED TO ALLOW FOR 2 TAPS TO BE INDEPENDENT BUT THE |
| | 2 SUPLY LINES MERGE BACK INTO ONE LINE BEFORE GOING TO |
| | THE INPUT CHAMBER OF THE FIRE PUMP. THE FIRE DEPATMENT |
| | REQUIRES IF THIS METHOD OF COMPLIANCE IS CHOSEN THAT |
| | THE 2 TAPS CONTINUE UNTIL THEY MANIFOLD BACK TOGETHER |
| | AS A MANAFOLD JUST BEFORE THE INTAKE OF THE FIRE PUMP. |
| | |
| | 7G) PROVISO: APPROVED BY FIRE CHIEF PROVIDED THAT THE |
| | EQUIPMENT FITS DOES NOT MEET THE SIZE REQUIREMENTS OF |
| | 911.1.3.THE LIFE SAFETY SHEET LEVEL 1 DOES NOT INDICATE |
| | COMPLIANCE WITH [F] 403.4.5 FIRE COMMAND. A FIRE |
| | COMMAND CENTER COMPLYING WITH SECTION 911 SHALL BE |
| | PROVIDED IN A LOCATION APPROVED BY THE FIRE DEPARTMENT. |
| | |
| | 7H-J) COMPLIED. |
| | |
| | 7K) MISSING INFORMATION: [F] 403.4.1 SMOKE DETECTION. |
| | SMOKE DETECTION SHALL BE PROVIDED IN ACCORDANCE WITH |
| | SECTION 907.2.13.1. |
| | |
| | 7L) MISSING INFORMATION: [F] 403.4.2 FIRE ALARM SYSTEM. |
| | A FIRE ALARM SYSTEM SHALL BE PROVIDED IN ACCORDANCE |
| | WITH SECTION 907.2.13. |
| | |
| | 7M) [F] 403.4.3 EMERGENCY VOICE/ALARM COMMUNICATION |
| | SYSTEM. AN EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM |
| | SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 907.5.2.2. |
| | |
| | 7N) [F] 403.4.4 EMERGENCY RESPONDER RADIO COVERAGE. |
| | EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN |
| | ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE. [F] |
| | 915.1 GENERAL. EMERGENCY RESPONDER RADIO COVERAGE SHALL |
| | BE PROVIDED IN ALL NEW BUILDINGS IN ACCORDANCE THE |
| | FLORIDA FIRE PREVENTION CODE. |
| | |
| | |
| | 7O) COMPLIED. 403.4.6 SMOKE REMOVAL. SMOKE CONTROL |
| | SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 909. |
| | |
| | 7P) REPEAT OF 7G. |
| | |
| | 7Q) MISSING INFORMATION: 403.6 ELEVATORS. |
| | ELEVATOR INSTALLATION AND OPERATION IN HIGH-RISE |
| | BUILDINGS SHALL COMPLY WITH CHAPTER 30 AND SECTIONS |
| | 403.6.1 AND 403.6.2. |
| | |
| | 7Q) 403.6.1 FIRE SERVICE ACCESS ELEVATOR. |
| | IN BUILDINGS WITH AN OCCUPIED FLOOR MORE THAN 120 FEET |
| | (36 576 MM) ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT |
| | VEHICLE ACCESS, A MINIMUM OF ONE FIRE SERVICE ACCESS |
| | ELEVATOR SHALL BE PROVIDED IN ACCORDANCE WITH SECTION |
| | 3007. |
| | 3007.4 FIRE SERVICE ACCESS ELEVATOR LOBBY. |
| | THE FIRE SERVICE ACCESS ELEVATOR SHALL OPEN INTO A FIRE |
| | SERVICE ACCESS ELEVATOR LOBBY IN ACCORDANCE WITH |
| | SECTIONS 3007.4.1 THROUGH 3007.4.4. |
| | |
| | EXCEPTION: WHERE A FIRE SERVICE ACCESS ELEVATOR HAS TWO |
| | ENTRANCES ONTO A FLOOR, THE SECOND ENTRANCE SHALL BE |
| | PERMITTED TO OPEN INTO AN ELEVATOR LOBBY IN ACCORDANCE |
| | WITH SECTION 708.14.1. |
| | |
| | 2ND REQUEST. 3007.4.1 ACCESS. THE FIRE SERVICE ACCESS |
| | ELEVATOR LOBBY SHALL HAVE DIRECT ACCESS TO AN EXIT |
| | ENCLOSURE. |
| | |
| | COMPLIED. 3007.4.2 LOBBY ENCLOSURE. |
| | THE FIRE SERVICE ACCESS ELEVATOR LOBBY SHALL BE |
| | ENCLOSED WITH A SMOKE BARRIER HAVING A MINIMUM 1-HOUR |
| | FIRE-RESISTANCE RATING, EXCEPT THAT LOBBY DOORWAYS |
| | SHALL COMPLY WITH SECTION 3007.4.3. |
| | |
| | EXCEPTION: ENCLOSED FIRE SERVICE ACCESS ELEVATOR |
| | LOBBIES ARE NOT REQUIRED AT THE STREET FLOOR. |
| | |
| | 2ND REQUEST. 3007.4.3 LOBBY DOORWAYS. EACH FIRE SERVICE |
| | ACCESS ELEVATOR LOBBY SHALL BE PROVIDED WITH A DOORWAY |
| | THAT IS PROTECTED WITH A 3/4-HOUR FIRE DOOR ASSEMBLY |
| | COMPLYING WITH SECTION 715.4. THE FIRE DOOR ASSEMBLY |
| | SHALL ALSO COMPLY WITH THE SMOKE AND DRAFT CONTROL DOOR |
| | ASSEMBLY REQUIREMENTS OF SECTION 715.4.3.1 WITH THE UL |
| | 1784 TEST CONDUCTED WITHOUT THE ARTIFICIAL BOTTOM SEAL. |
| | |
| | 2ND REQUEST, PROVIDE THE SQUARE FOOTAGE OF THE FIRE |
| | SERVICE ELEVATOR LOBBY. 3007.4.4 LOBBY SIZE. EACH |
| | ENCLOSED FIRE SERVICE ACCESS ELEVATOR LOBBY SHALL BE A |
| | MINIMUM OF 150 SQUARE FEET (14 M2) IN AN AREA WITH A |
| | MINIMUM DIMENSION OF 8 FEET (2440 MM). |
| | |
| | 7R) SHEET A8.00 WALL TYPES K-P DO NOT PROVIDE FIRE |
| | RATING OF WALL. |
| | |
| | 8-10) COMPLIED. |
| | |
| | 11) SHEET A2.03: |
| | 11A) THE PLANS DO NOT DEPICT ANY SHAFTS IN THE KITCHEN |
| | AREA FOR THE FUTURE KITCHEN EXHAUST & HOOD SYSTEM. |
| | 708.2 SHAFT REQUIED. SHEET A2.04 DOES SHOW NOT A 2 HOUR |
| | SHAFT BUT WHAT APPEARS TO BE 2 HOUR FIRE RATED DUCT |
| | WRAP. THIS DETAIL IS CONSISTENT UP THROUGH THE 10TH |
| | FLOOR. SEE M107 THE DUCT TURNS LEFT THEN UP AGAIN. |
| | ONTHE POOL DECK LEVEL IT IS SHOWN ON M107 IN THE R06 |
| | SEERVICE ROOM. ON THE POOL ROOF DECK PLAN A2.11 THE |
| | DUCT DOES NOT SHOW UP. DISCREPANCY IN PLANS. |
| | |
| | IF THERE IS TO BE NO 2 HR SHAFT, THEN A 2 HOUR DUCT |
| | WRAP WILL BE REQUIRED, PROVIDE THE MANUFACTURERES |
| | DETAILS, THE OTHER ISSUE IS NOT HAVING FIRE STOPPING |
| | DETAILS OF THE ASSEMBLY THROUGH THE RATED FLOOR PER |
| | 2010 FBC-B 713.3.1.2. THROUGH-PENETRATION FIRESTOP |
| | SYSTEMS. |
| | |
| | 11B-C) COMPLIED. |
| | |
| | 12) SHEET A2.11: |
| | |
| | 12A-B) COMPLIED. |
| | |
| | 12C) DEALS WITH THE STAIRS TO TTHE ELEVATOR EQUIPMENT, |
| | 2010 FBC-B 1009.14. THE RESPONSE INDICATES THE USE OF |
| | OTIS GEN 2 ELEVATIONS WHICH ARE MACHINELESS EQUIPMENT. |
| | PLEASE PROVIDE WHERE THE CONTROL PANEL FOR THE ELEVATOR |
| | IS TO BE LOCATED? IF IN RATED WALLS HOW WILL THE RATING |
| | BE MAINTAINED? 107.2.1.3. ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 12D) COMPLIED. |
| | |
| | 13) THE PRODUCT APPROVALS HAVE BEEN REQUESTED TO BE |
| | DEFERRED SUBMITTALS. 107.3.4.2 DEFERRED SUBMITTALS. FOR |
| | THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | PLEASE PROVIDE 3 SETS OF PRODUCT APPROVALS FOR EACH OF |
| | THE FOLLOWING COMPONENTS AND OR CLADDING. |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| | COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES & WATERPROOFING FOR |
| | SLABS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 14)PROVISO: 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 15) COMPLIED WIND DESIGN CRITERIA.. |
| | |
| | 16-20) COMPLIED. |
| | |
| | 20A) PROVISO: PLEASE ALSO NOTE THE 3 RD FLOOR IS TO BE |
| | DESIGNED FOR A FUTURE RESTARAUNT, BE AWARE OF 1013.2 |
| | WHERE FIXED SEATING MAY BE A HEIGHT FACTOR IN THE GUARD |
| | RAIL. |
| | |
| | 21) 2ND REQUEST. SHEET S1 AND S11.1 BOTH INDICATE THE |
| | USE OF AUGER CAST PILE, PLEASE PROVIDE WHAT AGENCY/ |
| | INSPECTION SERVICE WILL BE RESPONSIBLE FOR THEOBSERVING |
| | & RECORD KEEPING OF THE AUGER CAST PILE ASWELL AS LOAD |
| | TESTING TO SECTION 2010 FBC-B 1810.3.3.1.2. |
| | |
| | 22) 2ND REQUEST. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 23) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |