| Date |
Text |
| 2014-07-27 08:51:15 | GAS PLAN REVIEW |
| | PERMIT: 14061217 |
| | ADD: 335 CLEMATIS ST |
| | CONT: TBD |
| | TEL: (561)856-6655/ NEYITA |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: SUN. JULY 27/ 2014 |
| | ACTION: DENIED |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | NOTICE TO THE DESIGNER OF RECORD: |
| | CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A |
| | LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE |
| | FEE TO THE DESIGNER FOR PLAN REVIEW, IF PLANS ARE |
| | REJECTED THREE OR MORE TIMES FOR REPEATED FAILURE TO |
| | CORRECT A CODE VIOLATION. |
| | |
| | 1) SHEET P101 INDICATES THE USE OF A 2 LB. NATURAL GAS |
| | SYSTEM. THE PLANS SHOW THE NATURAL GAS SYSTEM INTRERING |
| | THE BUILDING WITHIN THE FPL VAULT. PLEASE CHECK WITH |
| | FPL, I DO NOT BELIEVE THEY WANT ANY OTHER UTILITES |
| | SHARING THEIR VAULT SPACE EXSPECIALLY A 2LB NATURAL GAS |
| | SYSTEM. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, 101.3 THE PURPOSE OF THIS CODE IS TO |
| | ESTABLISH THE MINIMUM REQUIREMENTS TO SAFEGUARD THE |
| | PUBLIC HEALTH, SAFETY AND GENERAL WELFARE THROUGH |
| | STRUCTURAL STRENGTH, MEANS OF EGRESS FACILITIES, |
| | STABILITY, SANITATION, ADEQUATE LIGHT AND VENTILATION, |
| | ENERGY CONSERVATION, AND SAFETY TO LIFE AND PROPERTY |
| | FROM FIRE AND OTHER HAZARDS ATTRIBUTED TO THE BUILT |
| | ENVIRONMENT AND TO PROVIDE SAFETY TO FIRE FIGHTERS, |
| | CODE OFFICIALS, AND EMERGENCY RESPONDERS DURING |
| | EMERGENCY OPERATIONS. |
| | |
| | 2) A SEPERATE GAS PERMIT WILL NEED TO BE APPLIED FOR, |
| | THE FUEL GAS REVIEW CAN TAKE PLACE UNDER THE PRIME |
| | (MASTER) PERMIT OR THE GAS CAN BE TAKEN OUT TOTALLY AND |
| | REVIEWED INDEPENDENTLY AS A SEPERATE PERMIT. |
| | |
| | 3) THERE ARE NO GAS PLANS, THE PLANS SUBMITTED DO NOT |
| | INDICATE WHAT TYPE OF FUEL THE FIRE PUMP AND GENERATOR |
| | ARE TO RUN ON PLEASE REVIEW THE MINIMUM PLAN REVIEW |
| | CRITERIA FOR A COMMERCIAL GAS PLAN REVIEW: |
| | |
| | GAS PERMIT APPLICATION REQUIREMENTS |
| | |
| | EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL |
| | BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING |
| | IN THE CITY OF WEST PALM BEACH: |
| | |
| | 3.1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL |
| | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER |
| | FBC-2010 FUEL GAS. |
| | |
| | 3.2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS |
| | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | 3.3. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | 3.4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD |
| | ON THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. |
| | 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35) |
| | |
| | 3.5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, |
| | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING |
| | AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ? |
| | USE OF CAPACITY SECTION A.3.1(4) |
| | |
| | 3.6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| | FBC-2010 FUEL GAS CODE SEC. 304 |
| | |
| | 3.7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010 |
| | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 |
| | PSI. |
| | |
| | 3.8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE |
| | AND TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS |
| | CODE SEC. 502 THRU 505. |
| | |
| | 3.9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2010 FUEL GAS SEC. 402.2 |
| | |
| | 3.10 2010 FBC-B 916.1 CARBON MONOXIDE PROTECTION. |
| | EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING |
| | BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| | ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR |
| | APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER |
| | FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE |
| | AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| | CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH |
| | ROOM USED FOR SLEEPING PURPOSES IN THE NEW BUILDING OR |
| | ADDITION, OR AT SUCH OTHER LOCATIONS AS REQUIRED BY |
| | THIS CODE. |
| | |
| | 916.1.1 CARBON MONOXIDE ALARM. |
| | THE REQUIREMENTS OF SECTION 916.1 SHALL BE SATISFIED BY |
| | PROVIDING FOR ONE OF THE FOLLOWING ALARM INSTALLATIONS: |
| | |
| | 1. A HARD-WIRED CARBON MONOXIDE ALARM. |
| | |
| | 2. A BATTERY-POWERED CARBON MONOXIDE ALARM. |
| | |
| | 3. A HARD-WIRED COMBINATION CARBON MONOXIDE AND SMOKE |
| | ALARM. |
| | |
| | 4. A BATTERY-POWERED COMBINATION CARBON MONOXIDE AND |
| | SMOKE ALARM. |
| | |
| | 916.1.2 COMBINATION ALARMS. |
| | COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE |
| | LISTED AND LABELED BY A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |