| Date |
Text |
| 2014-07-09 15:31:23 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1. PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND |
| | DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF |
| | NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| | REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| | PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| | OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| | |
| | 2. PER NFPA 241- STANDARD FOR SAFEGUARDING |
| | CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS, |
| | SECTION 4.2 TEMPORARY CONSTRUCTION TRAILERS SHALL BE |
| | SEPARATED FROM ADJACENT TRAILERS OR STRUCTURES IN |
| | ACCORDANCE WITH TABLE 4.2.1. PER TABLE 4.2.1: |
| | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 30 FEET |
| | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 35 FEET |
| | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 40 FEET |
| | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 45 FEET |
| | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 50 FEET |
| | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE |
| | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET |
| | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL |
| | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC |
| | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. |
| | |
| | 3. PROVIDE A DRAWING NOTES TO THE FUEL SUPPLY OF THE |
| | GENERATOR AND BOILER. |
| | |
| | 4. PROVIDE A DRAWING NOTE FOR PROVIDING AN EXTERIOR KEY |
| | SAFE TO ALLOW EMERGENCY RESPONDERS NON-FORCIBLE ENTRY |
| | INTO THE BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE |
| | CAN BE ORDERED FROM WWW.KNOXBOX.COM |
| | |
| | 5. PROVIDE A DRAWING NOTE FOR TACTILE SIGNAGE AT ALL |
| | REQUIRED EXIT DOORS WITH EXIT SIGNS. |
| | |
| | 6. PROVIDE A DRAWING NOTE FOR STAIRWAY IDENTIFICATION: |
| | NEW ENCLOSED STAIRS SERVING THREE OR MORE STORIES AND |
| | EXISTING ENCLOSED STAIRS SERVING FIVE OR MORE STORIES |
| | SHALL COMPLY WITH (A) THROUGH (L). |
| | (A) THE STAIRS SHALL BE PROVIDED WITH SPECIAL SIGNAGE |
| | WITHIN THE ENCLOSURE AT EACH FLOOR LANDING. |
| | (B) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL. |
| | (C) THE SIGNAGE SHALL INDICATE THE TERMINUS OF THE TOP |
| | AND BOTTOM OF THE STAIR ENCLOSURE. |
| | (D) THE SIGNAGE SHALL INDICATE THE IDENTIFICATION OF |
| | THE STAIR ENCLOSURE. |
| | (E) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL OF, AND |
| | THE DIRECTION TO, EXIT DISCHARGE. |
| | (F) THE SIGNAGE SHALL BE LOCATED INSIDE THE ENCLOSURE |
| | APPROXIMATELY 60-INCHES ABOVE THE FLOOR LANDING IN A |
| | POSITION THAT IS VISIBLE WHEN THE DOOR IS IN THE OPEN |
| | OR CLOSED POSITION. |
| | (G) THE FLOOR LEVEL DESIGNATION SHALL ALSO BE TACTILE. |
| | (H) THE SIGNAGE SHALL BE PAINTED OR STENCILED ON THE |
| | WALL OR ON A SEPARATE SIGN SECURELY ATTACHED TO THE |
| | WALL. |
| | (I) THE STAIRWAY IDENTIFICATION LETTER SHALL BE LOCATED |
| | AT THE TOP OF THE SIGN IN MINIMUM 1-INCH HIGH |
| | LETTERING. |
| | (J) SIGNAGE THAT READS ?NO ROOF ACCESS? AND IS LOCATED |
| | UNDER THE STAIRWAY IDENTIFICATION LETTER SHALL |
| | DESIGNATE STAIRWAYS THAT DO NOT PROVIDE ROOF ACCESS. |
| | LETTERING SHALL BE A MINIMUM OF 1-INCH HIGH. |
| | (K) THE FLOOR LEVEL NUMBER SHALL BE LOCATED IN THE |
| | MIDDLE OF THE SIGN IN MINIMUM 5-INCH HIGH NUMBERS. |
| | MEZZANINE LEVELS SHALL HAVE THE LETTER ?M? OR OTHER |
| | APPROPRIATE IDENTIFICATION LETTER PRECEDING THE FLOOR |
| | NUMBER, WHILE BASEMENT LEVELS SHALL HAVE THE LETTER ?B? |
| | OR OTHER APPROPRIATE IDENTIFICATION LETTER PRECEDING |
| | THE FLOOR LEVEL NUMBER. |
| | (L) IDENTIFICATION OF THE LOWER AND UPPER TERMINUS OF |
| | THE STAIRWAY SHALL BE LOCATED AT THE BOTTOM OF THE SIGN |
| | IN MINIMUM 1-INCH HIGH LETTERS OR NUMBERS. |
| | |
| | 7. SHEET A 1.01 & A 2.01 RETAIL MEZZANINE M22 SHALL NOT |
| | BE OCCUPIED UNTIL THE 2ND MEANS OF EGRESS IS PROVIDED |
| | FOR AND APPROVED. |
| | |
| | 8. CLARIFICATION AND CONSISTENCY IS REQUIRED REGARDING |
| | ELEVATOR LOBBY DOOR RATINGS: |
| | SHEET A 2.01 DOOR M21 IS RATED AND APPROVED. |
| | SHEET A 2.03 DOOR 326 IS NOT RATED. |
| | SHEET A 2.11 DOORS PD 10 & 10.1 ARE NOT RATED. |
| | SOME DOORS ARE LABLED CORRIDOR DOORS ON THE DOOR |
| | SCHEDULE, SOME ARE LABELD ELEVATOR LOBBY DOORS. PLEASE |
| | PROVIDE JUSTIFICATION. IT IS IMPERATIVE THAT EACH DOOR |
| | ASSOCIATED WITH |
| | AN ELEVATOR LOBBY ARE RATED AND INSTALLED CONSISTENTLY |
| | TO ENSURE EQUAL LIFE SAFETY IN THE SAME SPACES. |
| | |
| | 9. PROVIDE FOR CO MONITORING IN THE GENERATOR AND |
| | BOILER ROOMS. |
| | |
| | 10. SHEETS A 2.00, A 2.01, M101 & M102, DO NOT SHOW A |
| | VENTILATION SYSTEM IN THE PORTE COCHERE, DROP OFF |
| | AREAS. IT IS IMPERATIVE THAT THESE AREAS HAVE |
| | VENTIALTION PROVIDED FOR TO REMOVE ANY BUILDUP OF |
| | VEHICULAR GASES, CO. |
| | |
| | 11. SHEET FA 101 CO MONITORS ARE NEEDED FOR THE PORTE |
| | COCHERE, DROP OFF AREAS. SLEEPING ROOMS ARE DIRECTLY |
| | ABOVE THIS AREA AND IT IS IMPERATIVE THAT A PROTECTION |
| | SYSTEM IS PROVIDED TO REDUCE AND/OR ELIMINATE VEHICULAR |
| | GASES. |
| | |
| | 12. SHEET E 103 - ADD EXIT SIGN IN MAIN CORRIDOR |
| | POINTING DOWN CORRIDOR 236 TO STAIR NO. 1, 235. |
| | |
| | 13. SHEET E 104 - ADD EXIT SIGN IN HALLWAY OF EXTERIOR |
| | TERRACE 327, LEADING TO STAIR NO. 3, 312. |
| | - ADD EXIT SIGN OUTSIDE SOTH ELEVATOR LOBBY DOOR |
| | LEADING TO STAIR NO. 1, 371. |
| | |
| | 14. SHEET E 106 - ADD EXIT SIGN AT SOUTH CORRIDOR |
| | DIVIDER HEADER LEADING TO STAIR NO. 1, 518. ( COPY THIS |
| | EXIT SIGN AS PROVIDED FOR SAME LOCATION ON SHEET E 105) |
| | - ADD EXIT SIGN AT NORTH CORRIDOR HEADER LEADING TO |
| | STAIR NO. 2, 513. ( COPY THIS EXIT SIGN AS PROVIDED FOR |
| | SAME LOCATION ON SHEET E 105) |
| | |
| | 15. SHEET 107 - REMOVE EXIT SIGN IN ELEVATOR LOBBY |
| | PD10, SOUTH DOOR LOCATION (NO EXIT) AND ADD EXIT SIGN |
| | ON SUN DECK PD17, SIDE OF DOOR. |
| | - ADD EXIT SIGN INSIDE ELEVATOR LOBBY PD10, AT NORTH |
| | SIDE DOOR. |
| | - ADD EXIT SIGN AT NORTH SIDE OF SEATING PD12, LEADING |
| | TO POOL DECK AREA. |
| | - ADD EXIT SIGN AT NORTH SIDE OF SUN DECK PD17 AT THE |
| | SEATING AREA LEADING THROUGH SEATING AREA TO POOL DECK. |
| | - ADD EXIT SIGN AT NORTH SIDE OF POOL DECK PD02, |
| | LEADING TO NORTH EXIT STAIR PD01. EXIT SIGN SHALL BE |
| | VISABLE FROM SOUTH POOL DECK AREA. |
| | - ADD EXIT SIGN AT SOTH SIDE OF POOL DECK LEADING TO |
| | NORTH EXIT STAIR PD07. EXIT SIGN SHALL BE VISABLE FROM |
| | NORTH SIDE OF POOL DECK AREA. |
| | |
| | 16. NO UPPER ROOF ACCESS/EGRESS IS NOTED OR READILY |
| | IDENTIFIABLE. PLEASE PROVIDE FOR ACCESS/EGRESS. |
| | |
| | |
| | |
| | |