| 2014-08-06 14:07:57 | DATE: 8/6/2014 |
| | PROJECT: CLEMATIS HOTEL |
| | PERMIT#: 14061217 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) THE PRIMARY PERMIT SUBMITTAL INCLUDES A FLORIDA |
| | ENERGY EFFICIENCY CODE SUBMITTAL THAT INDICATES |
| | COMPLIANCE WITH THE FBC FOR ENERGY. HOWEVER, THE PLANS |
| | DO NOT REFLECT FULL COMPLIANCE. INDICATE FULL |
| | COMPLIANCE ON THE ELECTRICAL PLANS AS FOLLOWS: |
| | 2) PROVIDE A LIGHTING FIXTURE SCHEDULE, ACCOMPANIED BY |
| | MANUFACTURER EQUIPMENT SUBMITTALS AND SHOP DRAWINGS ON |
| | LIGHTING CONTROL AND/OR ENERGY MANAGEMENT SYSTEMS. FBC |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS |
| | 3) SHEET E101 |
| | SEE CODE REFERENCE: FBC-E 505.2 LIGHTING CONTROLS |
| | (MANDATORY). LIGHTING SYSTEMS SHALL BE PROVIDED WITH |
| | CONTROLS AS REQUIRED IN SECTIONS 505.2.1, 505.2.2, |
| | 505.2.3 AND 505.2.4 |
| | A.) LOBBY AND SERVICE CORRIDORS. INDICATE COMPLIANCE |
| | WITH FBC-E 505.2.2 AUTOMATIC LIGHTING SHUTOFF. |
| | B.) ELECTRICAL RM #110, FIRE PUMP RM #112, SHOULD NOT |
| | HAVE AN OS SWITCH DUE TO 505.2.2 EXCEPTION #4 SPACES |
| | WHERE AN AUTOMATIC SHUTOFF WOULD ENDANGER OCCUPANT |
| | SAFETY OR SECURITY. |
| | C.) THE PORTE COCHERE LIGHTING DOES NOT INDICATE ANY |
| | LIGHTING CONTROL FBC-E 505.2.4 EXTERIOR LIGHTING |
| | CONTROLS REQUIRED. |
| | D.) POLE LIGHTS AT FRONT ENTRY REQUIRE LIGHTING CONTROL |
| | AND WIND LOAD CALCULATIONS. FBC 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS |
| | E.) AC-R1.1 DOES NOT INDICATE A CIRCUIT OR A |
| | DISCONNECT. DISCONNECTING MEANS SHALL BE LOCATED WITHIN |
| | SIGHT FROM AND READILY ACCESSIBLE FROM THE |
| | AIR-CONDITIONING OR REFRIGERATING EQUIPMENT. THE |
| | DISCONNECTING MEANS SHALL BE PERMITTED TO BE INSTALLED |
| | ON OR WITHIN THE AIR-CONDITIONING OR REFRIGERATING |
| | EQUIPMENT. NEC 440.14 |
| | |
| | 4) SHEET E 102 |
| | A.) GENERATOR RM #M10 AND THE BOILER RM #M01 SHOULD NOT |
| | HAVE AN OS SWITCH DUE TO 505.2.2 EXCEPTION #4 SPACES |
| | WHERE AN AUTOMATIC SHUTOFF WOULD ENDANGER OCCUPANT |
| | SAFETY OR SECURITY. 505.2.4 |
| | |
| | 5) SHEET E103 AND SHEET E 201 |
| | SLEEPING ROOMS IN HOTELS REQUIRE LIGHTING CONTROL. |
| | FBC-E 505.2.1.3 ADDITIONAL CONTROLS. (3) |
| | |
| | 6) SHEET E 104 |
| | A.) INDICATE COMPLIANCE WITH FBC-E 505.2.2 AUTOMATIC |
| | LIGHTING SHUTOFF. |
| | B) INDICATE CIRCUITS FOR EXIT AND EMERGENCY LIGHTING. |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | |
| | 7) SHEET E 108 |
| | A.) ADDITIONAL GFI SERVICE OUTLETS ON THE ROOF FOR |
| | MECHANICAL EQUIPMENT. THE RECEPTACLE SHALL BE LOCATED |
| | ON THE SAME LEVEL AND WITHIN 25FT OF THE HEATING, |
| | AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. SEE NEC |
| | 210.63, 210.8(A)(3), AND 406.8(B)(1), |
| | |
| | 8) SHEET E 401 |
| | A.) NOTE 4 INDICATES TO REFER TO PANEL SCHEDULES FOR |
| | FEEDER SIZE. PANEL MDPAC CALLS FOR 4 RUNS OF 4, 500 |
| | KCMIL AL BUT ALSO CALLS FOR A 400AMP SERVICE RATED MCB |
| | WITH A CONNECTED LOAD OF 136AMPS PER PHASE. |
| | CLARIFICATION IS REQUIRED. FBC 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS |
| | B.) NOTE 6 INDICATES THE FIRE PUMP IS A 100HP 208V |
| | 3PHASE MOTOR. A 100 HP FIRE PUMP MOTOR REQUIRES A |
| | MINIMUM 400AMP SERVICE RATED OCPD AND FEEDER. RATE FIRE |
| | PUMP CONTROLLER AND FEEDERS PER NEC 695. SUBMIT |
| | MANUFACTURER DOCUMENTATION ON FIRE PUMP MOTOR AND |
| | CONTROLER/ATS |
| | C.) NOTE 13 INDICATES TO FEED THE 100HP FIRE PUMP FROM |
| | GENERATOR WITH #2 WIRE. AS STATED ABOVE A 100HP MOTOR |
| | REQUIRES A MUCH LARGER FEEDER. REVISE DESIGN FOR CODE |
| | COMPLIANCE. SEE NEC 310, 430, 695, AND 700 |
| | D.) NOTE 17 INDICATES TO FEED THE 100HP FIRE PUMP FROM |
| | UTILITY WITH #2 WIRE. AS STATED ABOVE A 100HP MOTOR |
| | REQUIRES A MUCH LARGER FEEDER. THERE IS NO INDICATION |
| | OF A METER AHEAD OF THIS UTILITY FEEDER. REVISE DESIGN |
| | FOR CODE COMPLIANCE. SEE NEC 215, 225, 230.2, 310, 430 |
| | AND 695. |
| | E) NOTE 20 INDICATES THE GENERATOR WILL COMPLY WITH |
| | NFPA 101 AMONG OTHERS ETC... PLEASE ADD 2008 EDITION OF |
| | NFPA 70, ARTICLE 700. |
| | F.) NOTE 22 CALL OUT A GENERATOR BUT DOES NOT IDENTIFY |
| | THE SIZE AND TYPE. IDENTIFY THE GENERATOR WITH VOLTAGE, |
| | KVA/KW SIZE ADEQUATELY TO SUPPORT ALL DESIGN LOADS AND |
| | PROVIDE MANUFACTURER EQUIPMENT SUBMITTALS ON THE |
| | GENERATOR AND ATS AS SUPPORTING DOCUMENTATION. |
| | G.) NOTE 39 INDICATES THIS SPACE TO BE THE FPL UTILITY |
| | VAULT. THE NAME DESIGNATION ABOVE THIS ROOM IS |
| | GENERATOR ROOM. CLARIFICATION IS REQUIRED. FBC 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS |
| | H.) PANEL 1L INDICATES IT IS TO BE FED FROM PANEL |
| | MDPAC. THERE IS NO LOAD INDICATED IN PANEL MDPAC ON |
| | SHEET E 501. I BELIEVE THE INTENT WAS TO INDICATE THE |
| | FEED FROM PANEL MDPA HOWEVER THERE IS NO LOAD INDICATED |
| | IN PANEL MDPA EITHER. THEREFORE THERE HAS BEEN NO LOAD |
| | CALCULATED. |
| | I.) THE RISER DIAGRAM INDICATES TO REFERENCE THE PANEL |
| | SCHEDULE FOR FEEDER SIZES. WHEN I REFERENCE PANEL MDPA |
| | OR MDPAC FOR FEEDER SIZES FOR PANELS 2L, 3L, 4L ETC... |
| | OR PANEL 2AC, 3AC, 4AC, ETC... THE NOTE IS THE SAME. TO |
| | REFERENCE THE PANEL SCHEDULE FOR FEEDER. THERE ARE NO |
| | PANEL SCHEDULES ON ANY OF THE E SHEETS FOR ANY OF THE |
| | FLOOR PANELS 2L, 3L,4L ETC..., 2AC, 3AC, 4AC, ETC..., |
| | 2R,3R, PROVIDE ALL PANEL SCHEDULES, LOADS AND FEEDERS. |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | J.) LOAD CALCULATIONS ARE REQUIRED FOR THE BUILDING |
| | ELECTRICAL SYSTEM BASED ON THE NEC ARTICLE 220. FBC |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS |
| | K.) IDENTIFY ALL SERVICE METERS AND MAINS. NEC 225.37 |
| | IDENTIFICATION. |
| | L.) INDICATE THE REQUIRED SIGNAGE INSIDE AND OUTSIDE |
| | THE BUILDING AS REQUIRED TO IDENTIFY THE GENERATOR AS |
| | AN ALTERNATE SOURCE OF POWER. NEC 700.8 NEC 225.37 |
| | IDENTIFICATION. |
| | M.) PROVIDE MANUFACTURER EQUIPMENT PRODUCT SUBMITTALS |
| | FOR THE GENERATOR, ATS AND RELATED EQUIPMENT. FBC |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS |
| | N) PROVIDE AND INDICATE THE TESTING AND MAINTENANCE |
| | REQUIRED PER NEC 700 |
| | O.) THERE IS A RUN IDENTIFIED AS 2, 4? EC (EMPTY |
| | CONDUITS) FROM AN UNIDENTIFIED SOURCE NEXT TO |
| | UNIDENTIFIED FPL UTILITY METER? THIS APPEARS TO |
| | REPRESENT A FUTURE METER FOR A FUTURE TENANT IN WHAT IS |
| | IDENTIFIED AS A FUTURE RETAIL SPACE. CLARIFICATION IS |
| | REQUIRED. REVISE PLANS TO MAINTAIN GROUPING AND MAXIMUM |
| | NUMBER OF MAINS. NEC 225.33 MAXIMUM NUMBER OF |
| | DISCONNECTS, AND 225.34 GROUPING OF DISCONNECTS. |
| | P.) PANEL K IS INDICATED ON THE THIRD LEVEL. THERE IS |
| | NO MAIN INDICATED IN FRONT OF OR GROUPED WITH THE REST |
| | OF THE MAINS IN THE MAIN ELECTRICAL ROOM. CLARIFICATION |
| | IS REQUIRED. REVISE PLANS TO MAINTAIN GROUPING AND |
| | MAXIMUM NUMBER OF MAINS. NEC 225.33 MAXIMUM NUMBER OF |
| | DISCONNECTS, AND 225.34 GROUPING OF DISCONNECTS. |
| | |
| | 9) SHEET E 502 |
| | A.) PANEL RAC IS IDENTIFIED AS A 1200AMP MLO PANEL WITH |
| | A 110AMP SUPPOSED LOAD FED WITH ONE SET OF 4, 250KCMIL |
| | AL W,1#4AL GRND FROM AN UNIDENTIFIED MAIN IN THE MAIN |
| | ELECTRICAL ROOM. IDENTIFY THE MAIN AS MAIN #? OF 6? |
| | IDENTIFY ALL SERVICE METERS AND MAINS. |
| | |
| | 10) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION |
| | FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| | 110.16, 110.22 |
| | |
| | 11) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. NEC 110.9 |
| | |
| | 12) PROVIDE SEPARATE ELECTRICAL PERMIT APPLICATIONS |
| | ACCOMPANIED BY MANUFACTURERS EQUIPMENT SUBMITTALS, |
| | PLANS, AND SHOP DRAWINGS AS REQUIRED FOR: GENERATOR, |
| | FIRE ALARM, SECURITY, CCTV, DATA/COM, NETWORK, |
| | STRUCTURED CABLING, AUDIO/VIDEO, LIGHTNING PROTECTION |
| | AND SIGNAGE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT /WP-CONTENT/UPLOADS/SITES/33 |
| | /2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |
| | |